BLD96-00002
| INSP-Alarm Testing | 11/19/1997 | 11/19/1997 | 11/19/1997 12:00:00 AM | A | PART |
|
|
tested duct detectors for air handlers - passed. tested smoke detectors in 2nd floor corridor, smoke dampers operated - passed. tested strobes/alarms in 2nd floor bullpen - passed.
|
BLD97-01254
| INSP-Final Inspection | 11/19/1997 | 11/19/1997 | 11/19/1997 12:00:00 AM | A | PASS |
|
|
c/o approved. corrections completed.
|