Inspections for the day of: Thursday, November 19, 1998.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE98-02865 INSP - Final11/19/199811/19/199811/19/1998 12:00:00 AM PASS
/ / 315 - t/s ok
ELE98-04071 INSP - Final11/19/199811/19/199811/19/1998 12:00:00 AM FAIL
/ / 315 - nr line and load reversed at meter
ELE98-02865 INSP - Electrical Rough-In11/18/199811/19/199811/19/1998 12:00:00 AMAPASS
11/18/98 315 - Scheduled by Hello!. Contact phone is [3857310]. ok
ELE98-01790 INSP - Electrical Rough-In11/18/199811/19/199811/19/1998 12:00:00 AMAPART
11/18/98 315 - Scheduled by Hello!. Contact phone is [8883124]. ok 2nd, and 3rd floor exterior walls and basement bathrooms
ELE98-03790 INSP - Electrical Rough-In11/18/199811/19/199811/19/1998 12:00:00 AMAFAIL
11/18/98 315 - Scheduled by Hello!. Contact phone is [3857310]. Joe's corrections have not been made jf
ELE98-03889 INSP - Final11/18/199811/19/199811/19/1998 12:00:00 AMAPASS
11/18/98 315 - ALAN ###-#### CHANGED FROM UG TO OVERHEAD-REINSPECT ok t/s
ELE98-04062 INSP - Final11/18/199811/19/199811/19/1998 12:00:00 AMAPASS
11/18/98 315 - ANNETTA ###-#### TEMP POLE ok
ELE98-04067 INSP - Final11/18/199811/19/199811/19/1998 12:00:00 AMAPASS
11/18/98 315 - A/C ONLY...BETTY ###-#### ok
ELE98-03806 INSP - Final11/19/199811/19/199811/19/1998 12:00:00 AMPFAIL
11/19/98 315 - LARRY ###-#### TEMP POLE cor. posted 250-83(c) short grd rod
ELE98-02379 INSP - Final11/19/199811/19/199811/19/1998 12:00:00 AMPPASS
11/19/98 315 - DOOR OPEN...###-#### EMMITT ok
ELE98-03438 INSP - Electrical Rough-In11/19/199811/19/199811/19/1998 12:00:00 AMPFAIL
11/19/98 315 - ALAN ###-#### cor. posted 250-72 needs to bond service m
ELE98-04071 INSP - Final11/19/199811/19/199811/19/1998 12:00:00 AMPPASS
11/19/98 315 - tom herman ###-#### ok correction made p/s 200a