Inspections for the day of: Tuesday, November 19, 2002.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-03582 Temporary Service11/18/200211/19/200211/19/2002 12:00:00 AMAPASS
###-####
T/S U/G Ok 11/19/2002 11:25:52 AM
ELE02-03145 Final11/18/200211/19/200211/19/2002 12:00:00 AMANR
###-#### annette
move service, reversed polarity, inuse covers, furnace disconnect.
had conf. 11/19/2002 11:10:08 AM
ELE02-03222 Electrical Rough-In11/18/200211/19/200211/19/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/18/2002 at 12:53:31. Contact: ###-####.
$42 fee due corrections not made.NEC 300.4 11/19/2002 10:44:09 AM
ELE02-03593 Rough-In Permanent Service11/18/200211/19/200211/19/2002 12:00:00 AMAFAIL
###-####
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.
11/19/2002 9:23:06 AM
ELE02-03543 Final11/18/200211/19/200211/19/2002 12:00:00 AMAPASS
###-####
P/S O/H R Ok 11/19/2002 9:04:38 AM
ELE02-03593 Permanent Service11/19/200211/19/200211/19/2002 12:00:00 AMAPASS
P/S U/G N Ok
ELE02-03222 Electrical Rough-In11/19/200211/19/200211/19/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 11/19/2002 at 09:52:58. Contact: ###-####.
ELE02-03593 Electrical Rough-In11/19/200211/19/200211/19/2002 12:00:00 AMPPASS
jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ELE02-02758 Electrical Rough-In11/19/200211/19/200211/19/2002 12:00:00 AMPPASS
R/I of no/west corner ok
ELE02-03562 Permanent Service11/15/200211/19/200211/19/2002 12:00:00 AMPPART
kevin- ###-####
P/S U/G R Ok 11/19/2002 1:58:08 PM
ELE02-03577 Electrical Rough-In11/19/200211/19/200211/19/2002 12:00:00 AMPFAIL
LORREN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
300.18 Raceway Installations.
(A) Complete Runs. Raceways, other than busways or exposed raceways having hinged or removable covers, shall be installed complete between outlet, junction, or splicing points prior to the installation of conductors
314.29 Boxes and Conduit Bodies to Be Accessible.
Boxes and conduit bodies shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building
300.14 Length of Free Conductors at Outlets, Junctions, and Switch Points.

300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.

300.11 Securing and Supporting.
(C) Cables Not Used as Means of Support. Cable wiring methods shall not be used as a means of support for other cables, raceways, or nonelectrical equipment.
11/19/2002 3:11:06 PM
ELE02-01572 Final11/19/200211/19/200211/19/2002 12:00:00 AMPPASS
###-#### ###-####
ELE02-02758 Final11/18/200211/19/200211/19/2002 12:00:00 AMPCANC
COVER INSPECTION FOR WEST CORNER OF OFFICE BUILDING, PART NOT PREVIOUSLY INSPECTED; Phone #: ###-#### Internet Inspection Request from: KATHY BYNUM
not a final 11/19/2002 3:41:21 PM