Inspections for the day of: Friday, November 19, 2004.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00644 INSP-Sprinkler Rough-in11/18/200411/19/200411/19/2004 12:00:00 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Okay to cover; will close this out at building final to verify escutcheons 11/19/2004 9:52:31 AM
BLD04-01896 FIRE-Conference11/19/200411/19/200411/19/2004 12:00:00 AMAPART
Met with owner after meeting with Sam Rogers - the paint booth shall comply with IFC 1504, the PIV and anti-freeze comtrol valves aren't supervised and a flow switch shall be installed on riser and monitored at FACP in Shakespeare as the fire pump is monitored at this panel, sprinkler plans needed for addition of heads under overhead doors and to replace heads near unit heaters, remove deadbolts at man doors in shop area, need extinguishers, sprinkler system requires annual inspection, left correction notice on front window 11/19/2004 11:09:16 AM