Inspections for the day of: Friday, November 19, 2004.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00692 INSP-Final Inspection11/18/200411/19/200411/19/2004 12:00:00 AMAFAIL
Per Sam Rogers a short corridor is lacking in a/v coverage. 11/19/2004 8:12:21 AM
BLD04-02386 FIRE-Final Inspection11/18/200411/19/200411/19/2004 12:00:00 AMACANC
Per Sam Rogers area is ok to occupy but still need fire alarm finaled 11/19/2004 8:13:01 AM
FIR04-00717 INSP-Final Inspection11/18/200411/19/200411/19/2004 12:00:00 AMAFAIL
Gas valve did not work. Need balance reports 11/19/2004 1:56:39 PM
BLD04-01984 FIRE-Final Inspection11/18/200411/19/200411/19/2004 12:00:00 AMAFAIL
Need to final fire alarm. Provide canopies for pendants and ceiling tile. Notified general contractor that he could not install manual flush bolt on the door the separates the counter from the kitchen 11/19/2004 2:00:14 PM
MIS04-00273 FIR-Final11/18/200411/19/200411/19/2004 12:00:00 AMAPASS
Fire alarm inspected and tested by Mary and Steve. System operated correctly per Mary 11/18/2004 3:08:53 PM
FIR04-00501 INSP-Final Inspection11/18/200411/19/200411/19/2004 12:00:00 AMPCANC
FIR04-00700 INSP-Sprinkler Rough-in/Hydro11/18/200411/19/200411/19/2004 12:00:00 AMPPASS
Underground supply line is ok to cover 11/19/2004 2:36:55 PM
BLD04-00809 FIRE-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPCANC
Don't know where this inspection came from. It was finaled by bob archibald on 11/15/04. Fire life safety was ok 11/19/2004 2:22:28 PM
BLD03-02970 FIRE-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPFAIL
Return bends on sprinkler pendants not insulated correctly. Provide approved door hardware on southeast door and double doors into exercise room. Provide exit discharge lighting on the northwest exit. Paint curbing as discussed. 11/19/2004 2:30:21 PM
BLD04-00026 FIRE-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPFAIL
Return bends on sprinkler pendants not insulated correctly. Provide approved door hardware on southeast door and double doors into exercise room. Provide exit discharge lighting on the northwest exit. Paint curbing as discussed. 11/19/2004 2:30:28 PM
BLD04-00028 FIRE-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPFAIL
Return bends on sprinkler pendants not insulated correctly. Provide approved door hardware on southeast door and double doors into exercise room. Provide exit discharge lighting on the northwest exit. Paint curbing as discussed. 11/19/2004 2:30:34 PM
BLD04-02164 FIRE-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPDONE
Mike ; Phone #: ###-#### Internet Inspection Request from: Jan Rice called back with new contact phone ###-#### Richard-error rescheduled
FIR04-00143 INSP-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPFAIL
Need to test hood and duct detectors to final 11/19/2004 3:07:45 PM
BLD04-02164 FIRE-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPPASS
fire life safety finaled 11/19/2004 3:37:06 PM
FIR04-00669 INSP-Final Inspection11/19/200411/19/200411/19/2004 12:00:00 AMPPASS
Fire alarm finaled