Inspections for the day of: Monday, November 19, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03880 Temporary Service11/19/200711/19/200711/19/2007 4:29:50 PMPFAIL
jeremy ###-#### cell

connect GEC to neut
clean equipment
tabs broken that hold breaker in place
connector required on GEC
ELE07-03856 Permanent Service11/19/200711/19/200711/19/2007 3:49:45 PMPPASS
jay Phone #: ###-####
P/S O/H N Ok
ELE07-03212 Permanent Service11/19/200711/19/200711/19/2007 3:40:15 PMPPASS
juan - please call 1/2 hr prior to inspection Phone #: ###-####
P/S U/G N Ok
ELE06-04412 Final11/13/200711/19/200711/19/2007 3:17:39 PMPFAIL
jim Phone #: ###-####
found 3 violations in the first few receps I checked
reversed polarity and no gfci protection of outside receps weather proof covers upside down
called tim and told him to plug test the house and recall it in.
ELE07-03132 Electrical Rough-In11/19/200711/19/200711/19/2007 2:41:45 PMPPASS
joanne Phone #: ###-####
ELE07-03818 Conference11/19/200711/19/200711/19/2007 1:49:15 PMPPART
aaron Phone #: ###-####
this was to be r/i
ELE07-03818 Electrical Rough-In11/19/200711/19/200711/19/2007 1:48:37 PMPCANC
aaron Phone #: ###-####
service not ready
R/I Ok
ELE07-03876 Rough-In Permanent Service11/19/200711/19/200711/19/2007 1:07:47 PMPPASS
gene Phone #: ###-####
R/I Ok
P/S U/G N Ok
ELE07-03860 Rough-In Permanent Service11/16/200711/19/200711/19/2007 10:54:25 AMAPASS
mike Phone #: ###-####
R/I Ok
P/s U/g N Ok
ELE07-03695 Final11/16/200711/19/200711/19/2007 9:27:43 AMAFAIL
dave Phone #: ###-#### Note: please call prior to inspection to meet with
great room ok
J-box not permited to mount on cover to another J-box
disconnect connect required for wires entering building from the roof
ELE07-03863 Electrical Rough-In11/18/200711/19/200711/19/2007 8:58:40 AMAPART
Please call Trent with any questions. Thanks. Trent Reagan
Phone #: ###-#### Internet Inspection Request from: Trent Reagan
great room only ok