Inspections for the day of: Monday, November 19, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01024 Final11/19/200711/19/200711/19/2007 4:11:56 PMPPASS
tyler Phone #: ###-#### ok to final
ELE07-03871 Conference11/16/200711/19/200711/19/2007 3:54:20 PMPDONE
Randall ###-#### hm. or ###-#### wk. talked about concrete encased electrode, u/g, service,box placement, make-up, circuits
ELE07-01624 Electrical Rough-In11/19/200711/19/200711/19/2007 3:20:42 PMPPASS
carl Phone #: ###-#### ok to cover stairs and ceilings anop
ELE07-03298 Electrical Rough-In11/19/200711/19/200711/19/2007 2:20:56 PMPPASS
Inspect west exterior wall (menu board area) Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contr, told to change address on permit to 6573, also told to sawcut u/g for inspection or can't use. ok to cover outside west board only for drive in area
ELE06-04665 Permanent Service11/19/200711/19/200711/19/2007 1:52:32 PMPFAIL
Larry Sanders (Dad) ###-#### //please call 30 min prior, needs to be there because 2 large dogs in yard met owner, left corr notice, nec 110.36 shall provide clearances in frontof electrical equipment in and out, 312.6 conductors shall not be deflected more than table allows, 250.52 shall provide grounding electrodes, Chapter 9 shall not overfill conduit, anote- shall make line and load at meter correct
ELE07-03841 Electrical Rough-In11/15/200711/19/200711/19/2007 12:42:05 PMPPASS
Steve (1st #) Jm (2nd #); Phone #: ###-#### or ###-#### Internet Inspection Request from: Cathy Weisshaupt called contractor, ric ok
ELE07-03712 Electrical Rough-In11/16/200711/19/200711/19/2007 10:46:33 AMAPASS
jessie Note: cover Phone #: ###-#### correction made, removed stop work tag, ric walls and hard lids only ok
ELE07-02302 Electrical Rough-In11/14/200711/19/200711/19/2007 10:00:02 AMAPASS
Contact: Steve Hess - underslab inspection please Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover slab 2nd floor anop
ELE07-01088 Electrical Rough-In11/16/200711/19/200711/19/2007 9:31:08 AMAPASS
sean Phone #: ###-#### hard lids only anop ok to cover
ELE07-02298 Final11/16/200711/19/200711/19/2007 8:43:48 AMAPASS
Contact: Brian Cornell Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok to final, ti contractor bringing in power, signed structural card
ELE07-03873 Temporary Service11/18/200711/19/200711/19/2007 8:26:58 AMAFAIL
Under ground temp pole Phone #: ###-#### Internet Inspection Request from: Lynn Cable caled, left correction notice, NEC there shall be no broken parts, terminal for gec and grounded service conductor