Inspections for the day of: Monday, November 19, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01261 FIRE-Final Inspection11/16/200711/19/200711/20/2007 8:56:47 AMAPART
A temporary occupancy was given with dave hannimans permission until the fire sprinkler drawings have been resubmitted and approved.
FIR07-00756 INSP-Final Inspection11/19/200711/19/200711/19/2007 4:42:03 PMPPART
A temporary occupancy was given by dave hanniman until the fire sprinkler drawings have been resubmitted and all changes approved including the new piping to the shed and roof top doghouses.
FIR07-00756 INSP-Final Inspection11/16/200711/19/200711/19/2007 4:40:56 PMAPART
A temporary occupancy was given by dave hanniman until the fire sprinkler drawings have been resubmitted and all changes approved including the new piping to the shed and roof top doghouses.
FIR07-00890 INSP-Final Inspection11/19/200711/19/200711/19/2007 3:54:21 PMPPASS
Permit finaled
FIR07-00849 INSP-Final Inspection11/16/200711/19/200711/19/2007 3:53:21 PMPPASS
Permit finaled
BLD06-01940 FIRE-Final Inspection11/14/200711/19/200711/19/2007 3:51:47 PMPFAIL
glen Phone #: ###-#### No sprinkler permit has been pulled and the sprinkler work is not complete. No inspection performed.
BLD07-01634 FIRE-Final Inspection11/16/200711/19/200711/19/2007 1:02:02 PMAPASS
life safety passed
FIR07-00809 INSP-Final Inspection11/16/200711/19/200711/19/2007 12:08:16 PMAPASS
permit finaled
BLD07-00948 FIRE-Final Inspection11/16/200711/19/200711/19/2007 11:05:54 AMAFAIL
Need the project related fire alarm permit finaled.
FIR07-00770 INSP-Alarm Testing11/15/200711/19/200711/19/2007 11:04:04 AMADONE
Need to test all audio/visuals, test duct smoke detectors and the flow alarm on the new dry pipe vavle did not sen a signal to the facp. I also need a print out of todays signals for verification.
BLD06-02010 FIRE-Final Inspection11/16/200711/19/200711/19/2007 10:34:01 AMAPART
A temporary occupancy was given with dave hannimans permission until the knox key box, which is on back order, is received and installed.
FIR07-00386 INSP-Alarm Testing11/16/200711/19/200711/19/2007 10:32:53 AMAPASS
Permit finaled
FIR07-00336 INSP-Final Inspection11/16/200711/19/200711/19/2007 10:32:17 AMAPASS
Permit finaled
BLD07-02297 FIRE-Final Inspection11/16/200711/19/200711/19/2007 9:56:02 AMAFAIL
The project related fire alarm permit needs finaled first.
FIR07-00919 INSP-Final Inspection11/16/200711/19/200711/19/2007 9:54:52 AMAFAIL
Per the fire alarm contractor the fire alarm system is not operational.