FIR12-00403
| FIR-Aging Inspection | 11/19/2012 | 11/19/2012 | 11/20/2012 8:31:35 AM | | DEFR |
|
|
Need site inspection request
|
FIR12-00328
| FIR-Aging Inspection | 11/19/2012 | 11/19/2012 | 11/20/2012 8:30:45 AM | | DEFR |
|
|
Need site inspection request
|
FIR12-00327
| FIR-Aging Inspection | 11/19/2012 | 11/19/2012 | 11/20/2012 8:30:13 AM | | DEFR |
|
|
Need site inspection request
|
BLD12-01915
| FIRE-Final Inspection | 11/19/2012 | 11/19/2012 | 11/19/2012 11:58:40 AM | P | CANC |
|
|
Cant final the life safety due to issues with the fire alarm permit
|
FIR12-00645
| INSP-Final Inspection | 11/19/2012 | 11/19/2012 | 11/19/2012 11:57:27 AM | P | FAIL |
|
|
The duct smoke detectors on zone 6 still are not reporting to the monitoring station.
|
FIR12-00423
| INSP-Sprinkler Rough-in | 11/16/2012 | 11/19/2012 | 11/19/2012 10:53:30 AM | A | FAIL |
|
|
See the city approved plans for locations where piping is not covered by the tenting material and heads are blocked by a wall in the restrooms. Also plans need to be resubmitted showing all of the elevation changes, additional elbows and the pipe routing changes.
|
FIR12-00658
| INSP-Final Inspection | 11/19/2012 | 11/19/2012 | 11/19/2012 10:43:55 AM | P | PASS |
|
|
Permit finaled.The smoke evac. system is a stand alone system that is not connected to the mall per Scott the electrician. I verified that several of the duct smoke detectors did shut down the hvac units and I also verified that the smoke detector at the mall/tenant entrance did shut the dampers at the hvac units upon alarm. These dampers are located on the second floor next to McDonalds.
|
FIR12-00658
| INSP-Alarm Testing | 11/16/2012 | 11/19/2012 | 11/19/2012 10:33:30 AM | A | DONE |
|
|
Scott Phone #: ###-####
|
BLD12-01747
| FIRE-Final Inspection | 11/16/2012 | 11/19/2012 | 11/19/2012 9:03:20 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00659
| INSP-Final Inspection | 11/16/2012 | 11/19/2012 | 11/19/2012 9:01:31 AM | A | PASS |
|
|
Permit finaled
|