Inspections for the day of: Wednesday, November 19, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03156 Rough-In Permanent Service11/19/201411/19/201411/19/2014 2:06:58 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
called Daniel
210.52A2(1)outlet required within first six feet of wall space
21052A2 outlet required wall space 2 foot or greater
210.11C3 bath outlet circuit shall supply not other outlets
210.52E3 required outlets, balconies shall have at least one receptacle
210.52H. Hallway 10 foot or greater shall have at least one receptacle
300.4A1 Nail plates required-bored holes less than 1-1/4 inch from edge of framing member
110.12 Mechanical execution of work, ground clamp is loose at grounding electrode
250.70 Only one wire allowed under ground clamp
250.68A- Ground clamp to be accessible
ELE14-03159 Final11/19/201411/19/201411/19/2014 12:59:13 PMPPASS
Kevin Phone #: ###-####
Inspections made, final OK
See permits ELE14-03086 and ELE14-03159
ELE14-03086 Final11/19/201411/19/201411/19/2014 12:58:48 PMPPASS
I will meet you onsite. I will call to schedule time slot . Phone #: ###-#### Inspection requested via web by Matthew Dunay
Inspections made, final OK
See permits ELE14-03086 and ELE14-03159
ELE14-02370 Final11/19/201411/19/201411/19/2014 12:24:37 PMPPASS
Phone #: ###-#### Inspection requested via web by John VanZandt
corrections made, final OK
ELE12-00913 ELE-Aging Inspection11/19/201411/19/201411/19/2014 12:24:11 PM DONE
Spoke to contractor, he will find out info for getting inspections
ELE14-03204 Electrical Rough-In11/19/201411/19/201411/19/2014 11:59:17 AMPPASS
contractor rescheduled from AM
Wall added between windows and hallway, OK to cover
ELE14-01966 Final11/18/201411/19/201411/19/2014 11:18:34 AMPFAIL
Call prior to going Phone #: 2084847804 >> Inspection requested via mobile web by Bryan Simpson

Needs GFI protection on 2 outdoor receptacles on playhouse in back yard. everything else has been checked. Spoke to owner
ELE14-02980 Electrical Rough-In11/19/201411/19/201411/19/2014 11:05:54 AMPPASS
Please call Eric with any issues Phone #: ###-#### Inspection requested via web by Eric Schroeder
RI, OK to cover
ELE14-03204 Electrical Rough-In11/18/201411/19/201411/19/2014 10:20:30 AMACANC
would like a mid morning inspection if possible. Phone #: ###-#### Inspection requested via web by John Edwards contractor moved to PM
ELE12-02301 ELE-Aging Inspection11/19/201411/19/201411/19/2014 9:45:20 AM DONE
called 11-19-14, 9:45 am ,no answer, phone does not have voicemail to leave a message.
ELE14-01685 Final11/18/201411/19/201411/19/2014 9:41:19 AMACANC
Phone #: ###-#### Inspection requested via web by Alan Lusk
left message for contractor, Fresh floors, building contractor would not let me on them , inspection cancelled
ELE14-01427 Final11/18/201411/19/201411/19/2014 9:38:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Burke Phone #: ###-####
FInal OK