ELE18-04448
| Electrical Rough-In | 11/19/2018 | 11/19/2018 | 11/19/2018 2:50:06 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Informed show window receptacles above doors with 10' of windows required by 210.62. Wall rough in ok cover
|
ELE18-04450
| Permanent Service | 11/19/2018 | 11/19/2018 | 11/19/2018 2:06:04 PM | P | FAIL |
|
|
New service needs inspected for change over. Phone #: ###-#### Inspection requested via web by Jake Cutler
110.24- Available fault current shall be posted with available fault current and date calculated prior to permanent service inspection.
|
ELE18-04161
| Electrical Rough-In | 11/16/2018 | 11/19/2018 | 11/19/2018 1:20:21 PM | A | PASS |
|
|
Please call Lynn at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor Conference room 182 square ft, Enter thru 225 N 9th entrance for access to elevators. Wall rough in ok cover
|
ELE18-02463
| Final | 11/16/2018 | 11/19/2018 | 11/19/2018 10:21:23 AM | A | FAIL |
|
|
Garage code 1862 Phone #: ###-#### Inspection requested via web by Therrin Robertson Unable to access panels due to stairs ablove and below marked do not use. Tread installation being done. 314.25- all boxes shall have covers. Open box in soffit north side of garage towards entry.
|
ELE18-04413
| Permanent Service | 11/15/2018 | 11/19/2018 | 11/19/2018 9:19:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Rough in done under permit ELE18-03487. Fuses rated 200k AIC. Available fault current shall be posted prior to final. p/s u/g n ok
|