Inspections for the day of: Monday, November 19, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04448 Electrical Rough-In11/19/201811/19/201811/19/2018 2:50:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Informed show window receptacles above doors with 10' of windows required by 210.62.
Wall rough in ok cover
ELE18-04450 Permanent Service11/19/201811/19/201811/19/2018 2:06:04 PMPFAIL
New service needs inspected for change over. Phone #: ###-#### Inspection requested via web by Jake Cutler

110.24- Available fault current shall be posted with available fault current and date calculated prior to permanent service inspection.
ELE18-04161 Electrical Rough-In11/16/201811/19/201811/19/2018 1:20:21 PMAPASS
Please call Lynn at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor
Conference room 182 square ft, Enter thru 225 N 9th entrance for access to elevators.
Wall rough in ok cover
ELE18-02463 Final11/16/201811/19/201811/19/2018 10:21:23 AMAFAIL
Garage code 1862 Phone #: ###-#### Inspection requested via web by Therrin Robertson
Unable to access panels due to stairs ablove and below marked do not use. Tread installation being done.
314.25- all boxes shall have covers. Open box in soffit north side of garage towards entry.
ELE18-04413 Permanent Service11/15/201811/19/201811/19/2018 9:19:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Rough in done under permit ELE18-03487.
Fuses rated 200k AIC. Available fault current shall be posted prior to final. p/s u/g n ok