Inspections for the day of: Monday, November 19, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00566 INSP-Alarm Testing11/19/201811/19/201811/19/2018 1:39:24 PMADONE
We tested the smoke detectors and notification devices today. All functioned except for the strobe in the back of Room 9. I also noted several doors that did not swing shut when the door mags released.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
BLD17-03833 FIRE-Final Inspection11/16/201811/19/201811/19/2018 1:06:27 PMAPART
The temporary has been extended to the 30th of this month so that the panic hardware can get installed and the other hardware removed.

Carson Phone #: ###-####
FIR18-00832 INSP-Sprinkler Rough-in11/16/201811/19/201811/19/2018 10:20:09 AMAPASS
Rough-in passed. Piping can be covered.

tom Phone #: ###-####
FIR18-00609 INSP-Sprinkler Rough-in11/19/201811/19/201811/19/2018 10:02:10 AMAPART
Need data sheets for the sprinkler heads to veriy their listed spacing/obstruction Phone #: ###-#### Inspection requirements. Need insulation removed from the BB1 heads in the attic. Need city approved plans for the changes/additions.

requested via web by Brett Lawatch
FIR18-00833 INSP-Sprinkler Rough-in11/16/201811/19/201811/19/2018 8:08:36 AMAPASS
Rough-in passed. Piping can be covered.

John Phone #: ###-####