FIR18-00566
| INSP-Alarm Testing | 11/19/2018 | 11/19/2018 | 11/19/2018 1:39:24 PM | A | DONE |
|
|
We tested the smoke detectors and notification devices today. All functioned except for the strobe in the back of Room 9. I also noted several doors that did not swing shut when the door mags released.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
BLD17-03833
| FIRE-Final Inspection | 11/16/2018 | 11/19/2018 | 11/19/2018 1:06:27 PM | A | PART |
|
|
The temporary has been extended to the 30th of this month so that the panic hardware can get installed and the other hardware removed.
Carson Phone #: ###-####
|
FIR18-00832
| INSP-Sprinkler Rough-in | 11/16/2018 | 11/19/2018 | 11/19/2018 10:20:09 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
tom Phone #: ###-####
|
FIR18-00609
| INSP-Sprinkler Rough-in | 11/19/2018 | 11/19/2018 | 11/19/2018 10:02:10 AM | A | PART |
|
|
Need data sheets for the sprinkler heads to veriy their listed spacing/obstruction Phone #: ###-#### Inspection requirements. Need insulation removed from the BB1 heads in the attic. Need city approved plans for the changes/additions.
requested via web by Brett Lawatch
|
FIR18-00833
| INSP-Sprinkler Rough-in | 11/16/2018 | 11/19/2018 | 11/19/2018 8:08:36 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
John Phone #: ###-####
|