Inspections for the day of: Tuesday, November 19, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02136 Electrical Rough-In11/18/201911/19/201911/19/2019 3:22:57 PMPPASS
Rough in please. Thank you. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott
Basement walls and bathroom hardlid rough in ok cover
ELE19-03664 Electrical Rough-In11/19/201911/19/201911/19/2019 2:37:03 PMPPASS
rough in of teller line Phone #: ###-#### Inspection requested via web by Tom Jenkins Informed general contractor must have access to all electrical due to all devices have been upgraded. Area noted rough in ok cover
MIS19-00391 ELE-Conference11/19/201911/19/201911/19/2019 2:06:39 PMPFAIL
BCC 4-0517- Unlawful electrical procedures-
(1)- It shall be unlawfull to alter any electrical wiring or equipment without first securing an electrical permit.
BCC 4-05-32- Code violations not to be retained.
334.12(B)(4)- NM cable shall not be installed in wet or damp locations. NM cable exposed on exterior of house with short sections of PVC conduits installed over it. Also under back patio and jump to outdoor sheds. Expose is a wet location, interior of a conduit is a damp location.
334.15(B)- NM cable shall not be installed where subject to physical damage. All expose wiring below 8' is subject to physical damage and shall be protected from accidental contact.
ELE19-03424 Final11/18/201911/19/201911/19/2019 12:39:11 PMAFAIL
Phone #: ###-#### Inspection requested via web by Tyler Ridley
110.3- 3 outdoor receptacle outlets not working. Not hot.
110.22- Furnace disconnecting means shall be identified.
334.30- Kitchen island, NM cable shall not be installed where subject to damage. Flex installed to protect NM cable shall protect entire length.
342.30- IMC service riser shall be secured in place with in 3' of meter/ panel combo.
356.30- Non-metallic flexible conduit below meter/ panel combo shall be secured with in 12" of termination.
ELE19-03094 Final11/18/201911/19/201911/19/2019 11:56:53 AMAFAIL
Phone #: ###-#### Inspection requested via web by Heath Thomas
314.16- Boxes shall have adequate space for all wiring and devices installed. Kitchen island receptacle serving counter top is a 8 cubic inch box with 11.25 cubic inches of conductor space installed.
ELE19-02061 Electrical Rough-In11/18/201911/19/201911/19/2019 11:18:14 AMAPASS
Mark Phone #: ###-####
Garage rough in ok cover