ELE19-02136
| Electrical Rough-In | 11/18/2019 | 11/19/2019 | 11/19/2019 3:22:57 PM | P | PASS |
|
|
Rough in please. Thank you. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott Basement walls and bathroom hardlid rough in ok cover
|
ELE19-03664
| Electrical Rough-In | 11/19/2019 | 11/19/2019 | 11/19/2019 2:37:03 PM | P | PASS |
|
|
rough in of teller line Phone #: ###-#### Inspection requested via web by Tom Jenkins Informed general contractor must have access to all electrical due to all devices have been upgraded. Area noted rough in ok cover
|
MIS19-00391
| ELE-Conference | 11/19/2019 | 11/19/2019 | 11/19/2019 2:06:39 PM | P | FAIL |
|
|
BCC 4-0517- Unlawful electrical procedures- (1)- It shall be unlawfull to alter any electrical wiring or equipment without first securing an electrical permit. BCC 4-05-32- Code violations not to be retained. 334.12(B)(4)- NM cable shall not be installed in wet or damp locations. NM cable exposed on exterior of house with short sections of PVC conduits installed over it. Also under back patio and jump to outdoor sheds. Expose is a wet location, interior of a conduit is a damp location. 334.15(B)- NM cable shall not be installed where subject to physical damage. All expose wiring below 8' is subject to physical damage and shall be protected from accidental contact.
|
ELE19-03424
| Final | 11/18/2019 | 11/19/2019 | 11/19/2019 12:39:11 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 110.3- 3 outdoor receptacle outlets not working. Not hot. 110.22- Furnace disconnecting means shall be identified. 334.30- Kitchen island, NM cable shall not be installed where subject to damage. Flex installed to protect NM cable shall protect entire length. 342.30- IMC service riser shall be secured in place with in 3' of meter/ panel combo. 356.30- Non-metallic flexible conduit below meter/ panel combo shall be secured with in 12" of termination.
|
ELE19-03094
| Final | 11/18/2019 | 11/19/2019 | 11/19/2019 11:56:53 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas 314.16- Boxes shall have adequate space for all wiring and devices installed. Kitchen island receptacle serving counter top is a 8 cubic inch box with 11.25 cubic inches of conductor space installed.
|
ELE19-02061
| Electrical Rough-In | 11/18/2019 | 11/19/2019 | 11/19/2019 11:18:14 AM | A | PASS |
|
|
Mark Phone #: ###-#### Garage rough in ok cover
|