Inspections for the day of: Friday, November 2, 2001.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-02641 ELE-Aging Inspection11/2/200111/2/200111/2/2001 12:00:00 AM PASS
sign looks ok no access to soffit 11/9/2001 3:39:06 PM
ELE01-02986 Final11/1/200111/2/200111/2/2001 12:00:00 AMAFAIL
correction called 310-15 table310-15(b) (2) (a) needs to derate wires in emt 11/2/2001 2:49:34 PM
ELE01-02989 Final11/1/200111/2/200111/2/2001 12:00:00 AMAFAIL
###-#### called contractor correction 310-15 deration of conductors in a raceway 11/2/2001 5:53:59 PM
ELE01-02992 Final11/1/200111/2/200111/2/2001 12:00:00 AMAFAIL
called contractor correction 310-15 deration of conductors in a raceway 11/2/2001 5:53:00 PM
ELE01-03640 Rough-In Permanent Service11/1/200111/2/200111/2/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/01/2001 at 15:37:29. Contact: ###-####. cor. and fee due posted called 300-4 1 1/4 11/2/2001 10:33:00 AM
ELE01-03124 Electrical Rough-In11/1/200111/2/200111/2/2001 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 11/01/2001 at 22:54:41. Contact: ###-####. partial one room ok the other owner has some work to do still see JF for details 11/2/2001 11:48:44 AM
ELE01-03697 Rough-In Permanent Service10/29/200111/2/200111/2/2001 12:00:00 AMAFAIL
###-#### STEVE cor. and fee due posted called 370-16 , and 300-4 1 1/4, nail plates 11/2/2001 10:32:18 AM
ELE01-03699 Electrical Rough-In10/29/200111/2/200111/2/2001 12:00:00 AMAFAIL
STEVE ###-#### ffe due , do not cover ,a nd correction posted called 300-4 1 1/4 inches 11/2/2001 2:45:23 PM
ELE01-02986 Electrical Rough-In11/2/200111/2/200111/2/2001 12:00:00 AMAPART
Added by Inspector: 315 On 11/2/2001 11:56:27 AM conference ok
ELE01-02639 Electrical Rough-In11/2/200111/2/200111/2/2001 12:00:00 AMPPART
Added by Inspector: 315 On 11/2/2001 4:43:11 PM concrete cover for electrode ok
ELE01-03116 Final11/2/200111/2/200111/2/2001 12:00:00 AMPFAIL
cor. posted 70-20 needs box extension, 336-6(b) protect romex in peninsular counter, 410-8 fixture shall be mounted 6ft above storage space as defined by 410-8(a) definitions did not call no call back # given 11/2/2001 3:33:35 PM
ELE01-03721 Final11/2/200111/2/200111/2/2001 12:00:00 AMPFAIL
###-#### JEAN cor. posted called remove bond screw at sub panel, and 110-26 remove phone cable from below p/s and from above sub panel in basement 11/2/2001 5:10:52 PM
ELE01-03138 Final11/2/200111/2/200111/2/2001 12:00:00 AMPPASS
###-#### PATRICK ok 11/2/2001 4:41:39 PM
ELE01-02639 Final11/2/200111/2/200111/2/2001 12:00:00 AMPCANC
###-#### PATRICK no final r/i for concrete encased electrode 11/2/2001 4:42:31 PM
ELE01-02254 Final11/2/200111/2/200111/2/2001 12:00:00 AMPPASS
###-#### PATRICK ok 11/2/2001 4:41:25 PM
ELE01-03695 Electrical Rough-In11/2/200111/2/200111/2/2001 12:00:00 AMPFAIL
###-#### MARTIN do not cover , correction, and $42.00 fee due posted called 300-4 nail plates and 1 1/4, and 336-18 shall not staple cables on edge 11/2/2001 2:06:38 PM
ELE01-03130 Final11/2/200111/2/200111/2/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 11/02/2001 at 10:01:00. Contact: ###-####. ok 11/2/2001 3:58:34 PM
ELE01-01772 Electrical Rough-In11/1/200111/2/200111/2/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 11/01/2001 at 12:01:26. Contact: ###-####. u/g for parking lot ok 11/2/2001 4:44:42 PM
ELE01-01772 Electrical Rough-In11/1/200111/2/200111/1/2001 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 11/01/2001 at 11:48:24. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 11/01/2001 at 12:00:07.