Inspections for the day of: Wednesday, November 2, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02806 Final11/2/200511/2/200511/2/2005 4:04:30 PMPPART
Late afternoon inspection if possible. Thanks.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen left corr notice,250 bond hot and cold water pipe,210.8 add gfci within 25' of rooftop unit, 408.4 add panel schedules, 210.8 gfci by sink 400.8 lite shall not be cord connected
ELE05-03971 Temporary Service11/2/200511/2/200511/2/2005 3:58:41 PMPPASS
###-#### darrell t/s u/g n ok
ELE05-03086 Final11/2/200511/2/200511/2/2005 3:19:29 PMPPASS
mike ###-#### ok to final
ELE05-03250 Final11/2/200511/2/200511/2/2005 1:51:38 PMPPASS
Scheduled by a contractor via Hello! on 11/2/2005 at 7:53:18 AM. Contact: ###-####. left survey with elect,408.4 ckt directory shall be correct, 352.30(A) rnc shall be strapped, 314.21 recpt covers shall not have gaps, 406.4(D) recpt faceplates shall be flush with rcpt, 422.16(B) cords shall be 18" to 36" if using disposals. Will check on next final. Signed occ card
ELE05-03773 Electrical Rough-In11/1/200511/2/200511/2/2005 9:41:46 AMANR
kendall; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no fa prints, so no piping done for same. elect ri ok. They will recall. Left corr notice,210.62 shall add show room rcpts over windows
ELE05-03702 Electrical Rough-In11/2/200511/2/200511/2/2005 12:00:00 AMAPASS
ok to cover fibre-optic dome soffit,left corr notice 210.62 show window recpts shall be installed directly over windows and for every 12'
ELE05-03780 Electrical Rough-In11/2/200511/2/200511/2/2005 12:00:00 AMAPART
left corr notice, 210.62 show room window recpt shall be added