BLD04-01324
| FIRE-Final Inspection | 11/1/2005 | 11/2/2005 | 11/3/2005 10:10:15 AM | A | NR |
|
|
Project is not ready for life safety inspection, several items remain incomplete.
|
FIR05-00265
| INSP-Alarm Testing | 11/2/2005 | 11/2/2005 | 11/2/2005 5:39:20 PM | P | PASS |
|
|
Underground fire supply line permit finaled.
|
FIR05-00265
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 5:34:49 PM | P | CANC |
|
|
Duplicate inspection already called in.
|
FIR05-00678
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 5:28:27 PM | P | PASS |
|
|
Fire alarm permitted work passed inspection.
|
FIR05-00600
| INSP-Sprinkler Rough-in | 11/2/2005 | 11/2/2005 | 11/2/2005 3:12:01 PM | P | PART |
|
|
Underground riser and 5' stub out only are acceptable to cover.
|
BLD05-00311
| FIRE-Final Inspection | 11/1/2005 | 11/2/2005 | 11/2/2005 1:46:24 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
BLD05-01706
| FIRE-Final Inspection | 11/1/2005 | 11/2/2005 | 11/2/2005 12:02:00 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00506
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 12:00:52 PM | P | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00728
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 11:28:08 AM | P | PASS |
|
|
Fire sprinkler permitted work passed inspection.
|
FIR05-00711
| INSP-Final Inspection | 11/1/2005 | 11/2/2005 | 11/2/2005 11:26:47 AM | A | PASS |
|
|
The three HSW at exterior canopy piped off the antifreeze loop are acceptable.
|
BLD05-02402
| FIRE-Final Inspection | 10/31/2005 | 11/2/2005 | 11/2/2005 10:12:21 AM | A | PASS |
|
|
Items have been corrected as discussed, fire life safety passed inspection.
|
BLD05-01279
| FIRE-Conference | 11/1/2005 | 11/2/2005 | 11/2/2005 10:05:18 AM | A | DONE |
|
|
On site discussion with the general contractor regarding door hardware requirements for exiting the express room, driver and dispatcher rooms.
|
FIR05-00593
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler passed final inspection.
|
FIR05-00623
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm passed inspection.
|
FIR05-00528
| INSP-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 12:00:00 AM | P | FAIL |
|
|
Provide resubmittals reflecting items 1 thru 9 on plan review notes, attatched outside mechanical room is not shown on plans, missing longitudinal brace on 21/2 " main, need 200 degree head in upstairs mech room and janitors room 1st floor, install relief valve at riser, need 911 sign, install head cage at SW in mech room, not all items reviewed at this time.
|