FIR06-00690
| INSP-Conference | 10/31/2006 | 11/2/2006 | 11/3/2006 9:00:34 AM | A | DEFR |
|
|
Phone #: ###-#### Internet Inspection Request from: Ken Campbell
|
FIR06-00545
| INSP-Final Inspection | 10/31/2006 | 11/2/2006 | 11/3/2006 9:00:18 AM | A | DEFR |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett
|
BLD05-03105
| FIRE-Final Inspection | 11/1/2006 | 11/2/2006 | 11/3/2006 8:59:22 AM | P | CANC |
|
|
Life safety final pending project related FIR permit finals.
|
FIR06-00795
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 4:29:01 PM | P | NR |
|
|
The shell fire alarm permit must be approved and finaled prior to inspection and final of this TI permit.
|
FIR06-00794
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 4:28:06 PM | P | NR |
|
|
The shell fire alarm permit must be approved and finaled prior to inspection and final for this TI permit.
|
FIR06-00793
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 4:27:04 PM | P | NR |
|
|
The shell fire alarm permit must be approved and finaled prior to inspection and approval of this TI permit.
|
BLD06-01534
| FIRE-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 4:25:48 PM | P | PASS |
|
|
Life safety passed field inspection.
|
FIR06-00662
| INSP-Sprinkler Rough-in | 11/2/2006 | 11/2/2006 | 11/2/2006 4:16:05 PM | P | PART |
|
|
UG fire supply line is okay to cover, contractor to backfill the annular space between the ductile riser pc. and the concrete stem wall/floor slab with approved material.
|
FIR06-00712
| INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 2:31:24 PM | A | NR |
|
|
Final pending shell permit completion.
|
FIR06-00695
| INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 2:30:54 PM | A | NR |
|
|
Final pending shell permit completion.
|
FIR06-00694
| INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 2:30:29 PM | A | NR |
|
|
Final pending shell permit completion.
|
FIR06-00375
| INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 2:29:19 PM | A | DEFR |
|
|
Pending unfinished alarm work.
|
FIR06-00507
| INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 2:27:24 PM | A | NR |
|
|
Per contractor the elevator shaft smoke and heat detectors are not yet installed.
|
BLD05-03105
| FIRE-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 2:26:06 PM | P | CANC |
|
|
Duplicate inspection request already called in.
|
FIR06-00691
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 2:05:07 PM | P | CANC |
|
|
No time available for inspection today, to be rescheduled per agreement with contractor.
|
FIR06-00589
| INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 2:01:27 PM | P | CANC |
|
|
No time to complete this inspection today, to be rescheduled per agreement with contractor.
|
FIR06-00810
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 1:58:48 PM | P | CANC |
|
|
No time available to complete this inspection request today, to be rescheduled per conversation with contractor.
|
FIR05-00402
| INSP-Sprinkler Rough-in/Hydro | 11/1/2006 | 11/2/2006 | 11/2/2006 1:55:15 PM | P | CANC |
|
|
No time to complete this inspection.
|
FIR05-00861
| FIR-Aging Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 1:53:19 PM | | PASS |
|
|
Work has been completed, no request for demo inspection was made.
|
FIR06-00502
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 1:14:47 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR06-00502
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 1:13:04 PM | A | PART |
|
|
Two of three items on the previous correction notice have been verified for completion including signage at the door to the FACP room and retest of the PIV tamper switch. The latching supervisory signals at the panel have been conditionally accetped for this project only by Boise City PDS department head B. Chatterton. Contractor failed to produce NFPA 72 record of completion forms at final testing, permit final pending correct documentation for acceptance signature.
|
BLD06-03001
| FIRE-Conference | 11/1/2006 | 11/2/2006 | 11/2/2006 1:04:07 PM | A | DONE |
|
|
On site confrence to discuss building modifications which may affect the fire sprinkler system, noted one area outside the new data room which is lacking proper coverage, project will require an FIR permit to complete this work.
|
BLD06-03000
| FIRE-Conference | 11/1/2006 | 11/2/2006 | 11/2/2006 1:01:06 PM | A | DONE |
|
|
On site confrence to discuss building modifications which may affect the fire sprinkler system.
|
FIR06-00468
| INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 12:31:30 PM | P | FAIL |
|
|
Several items need addressed, left a 6 item c/n on site including heads installed do not match the type system was designed for or submitted on, the single service supply as indicated has not been witnessed for flush see note #11, need to provide access to inspect the OH installation as no rough-in inspection was requested, there is a non-monitored shutoff valve upstream of the system controls and flow switch see note #13 for requirements, the WH closet needs an intermediate head installed, provide verification of the type of antifreeze used as this system is CPVC. NOTE: the sprinkler monitoring has been connected without a fire alarm permit.
|