ELE07-02734
| ELE-Aging Inspection | 11/2/2007 | 11/2/2007 | 11/5/2007 3:23:08 PM | | DONE |
|
|
|
ELE07-03568
| Final | 11/1/2007 | 11/2/2007 | 11/2/2007 4:49:31 PM | A | NR |
|
|
On-Site contact Mitch ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson final not ready called left message no response back
|
ELE07-03126
| Final | 11/2/2007 | 11/2/2007 | 11/2/2007 4:31:13 PM | P | PASS |
|
|
don Phone #: ###-####
|
ELE07-03513
| Final | 11/2/2007 | 11/2/2007 | 11/2/2007 4:10:28 PM | P | PASS |
|
|
tony Phone #: ###-#### ok
|
ELE07-03674
| Rough-In Permanent Service | 11/1/2007 | 11/2/2007 | 11/2/2007 2:00:41 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Tim Lawrence correction not made called explained again requirements for nail plates
|
ELE07-02834
| Permanent Service | 10/30/2007 | 11/2/2007 | 11/2/2007 1:13:16 PM | P | FAIL |
|
|
jared Phone #: ###-#### met contr T310.15(B)(6) needs 2/0 cu or 4/0 alum for 200 amp p/s, used #2 copper, 240.24 panel set 7" too high, shall be 6ft 7" too center of highest breaker space
|
ELE07-03678
| Permanent Service | 10/31/2007 | 11/2/2007 | 11/2/2007 12:18:55 PM | P | PASS |
|
|
Pat Gill contact ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis p/s u/g rec. ok
|
ELE07-02963
| Electrical Rough-In | 11/1/2007 | 11/2/2007 | 11/2/2007 11:07:40 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton see added p/s
|
ELE07-02963
| Permanent Service | 11/2/2007 | 11/2/2007 | 11/2/2007 11:07:22 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri p/s u/g new ok
|
ELE07-03528
| Final | 11/1/2007 | 11/2/2007 | 11/2/2007 11:06:33 AM | A | PASS |
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok c ard signed
|
ELE07-03163
| Final | 11/1/2007 | 11/2/2007 | 11/2/2007 11:06:04 AM | A | FAIL |
|
|
roger Phone #: ###-#### corr called 210.52(A) needs to add 4 outlets for wall space added walls
|
ELE07-02814
| Final | 11/1/2007 | 11/2/2007 | 11/2/2007 9:07:31 AM | A | PASS |
|
|
3 pole breakers installed for furniture and 4/11 boxes on riser secured. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok no card
|
ELE07-03563
| Final | 11/2/2007 | 11/2/2007 | 11/2/2007 8:54:57 AM | A | PASS |
|
|
repaired or removed unused wiring, cover boxes, installed light fixture wires for support. Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok card signed
|
ELE07-00267
| Final | 11/1/2007 | 11/2/2007 | 11/2/2007 8:20:12 AM | A | PASS |
|
|
judy Phone #: ###-#### ok
|