Inspections for the day of: Friday, November 2, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03706 Electrical Rough-In11/2/200711/2/200711/2/2007 4:00:33 PMPPASS
Robert ###-####//please come late afternoon, had emergency so requests inpsection after 4pm walls only ok to cover, hard lids not ready
ELE07-03694 Final11/2/200711/2/200711/2/2007 3:28:34 PMPFAIL
###-#### my # is in process of change. We need you to look at the bnew power supply to trailer Phone #: ###-#### Internet Inspection Request from: William Zerfas called, left correction notice,nec 550.10(B) strain relief shall be provided at panel for power supply cord, 400.8(6) flexible cord or cable shall not be installed in raceway, BCC all u/g shall be inspected before cover
ELE07-01437 Final11/2/200711/2/200711/2/2007 2:36:35 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contractor, left survey, NEC 250.104(A)(1) shall bond hot and cold water piping, BCC shall install receptacle on northwall, shop side of office, shall post address, no structural card to sign
ELE07-02940 Final11/2/200711/2/200711/2/2007 1:59:22 PMPPASS
Key to front door in exterior outlet at front door. Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final
ELE07-03000 Final11/2/200711/2/200711/2/2007 1:16:32 PMPPASS
dustin Phone #: ###-#### met contractor, ok to final
ELE07-03704 Conference11/2/200711/2/200711/2/2007 12:35:17 PMPDONE
Please call at least 15 mins prior to inspection--###-#### don talked about whether service will allow addition of hot tub or whether they need new service and bring up to code, fuse box in downstairs bath would have to change with new service
ELE07-00745 Conference11/1/200711/2/200711/2/2007 11:04:57 AMADONE
david Phone #: ###-#### reviewed circuits, afci for bedroom, 1 1/4" for holes and nm cable, make-up and when to call for ri inspection
ELE07-03486 Final11/1/200711/2/200711/2/2007 10:42:48 AMAPASS
andy Phone #: ###-#### ok to final
ELE07-03554 Final11/1/200711/2/200711/2/2007 10:09:14 AMAPASS
final on new service and wiring for A/C unit and furnace. Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to final
ELE07-03702 Electrical Rough-In11/1/200711/2/200711/2/2007 9:27:07 AMAPASS
need inspection on conduits from house to garage Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ok to cover u/g house to garage only
ELE07-03703 Electrical Rough-In11/1/200711/2/200711/2/2007 9:12:17 AMAPASS
need inspection on condiut from house to garage Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ok to cover u/g house to garage only
ELE07-03657 Conference11/1/200711/2/200711/2/2007 8:51:19 AMADONE
per mike kinner meet homeowner at 8- linda-- ###-#### work - or home ###-#### met owner and son-in-law, reviewed box fill, circuiting, listing for tub, 1 1/4" for holes and nm cable, nailplates, no nm stapled on edge, no screws in boxes to mount to framing members, ground for subpanel, ampacity for loads, whether or not listing allows #10 to be terminated on device, length of free conductor at box, water heater wiring, tub install wiring, make-up for ri inspection and when to call for inspection
ELE07-03492 Electrical Rough-In11/1/200711/2/200711/2/2007 8:03:42 AMAPASS
cover inspection pouring concrete in morning need asap Phone #: ###-#### Internet Inspection Request from: Tyler Bowen u/g ok to pour anop