Inspections for the day of: Tuesday, November 2, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00077 INSP-Final Inspection11/2/201011/2/201011/2/2010 3:33:23 PMPCANC
Cancelled due to time constraints and Guy and my schedule not matching. Guy is rescheduling for first thing in the morning.
FIR09-00012 INSP-Final Inspection11/2/201011/2/201011/2/2010 3:32:55 PMPCANC
Cancelled due to time constraints and Guy and my schedule not matching. Guy is rescheduling for first thing in the morning.
FIR09-00174 INSP-Final Inspection11/2/201011/2/201011/2/2010 3:32:18 PMPCANC
Cancelled due to time constraints and Guy and my schedule not matching. Guy is rescheduling for first thing in the morning.
FIR10-00522 INSP-Sprinkler Rough-in11/2/201011/2/201011/2/2010 3:30:44 PMPPASS
The sprinkler piping is ok to cover.
BLD10-02100 FIRE-Final Inspection11/1/201011/2/201011/2/2010 2:48:09 PMAFAIL
Provide annual inspection for all fire extinguishers, provide exit discharge lights at the three exits, provide correct remote annunciators or meet the exception of IMC 606.2
BLD10-02101 FIRE-Final Inspection11/1/201011/2/201011/2/2010 2:45:14 PMAFAIL
Provide annual inspection all of the fire extinguishers and repair or remove the exit sign.
FIR10-00489 INSP-Final Inspection11/2/201011/2/201011/2/2010 1:35:28 PMPPASS
Permit finaled
FIR10-00400 INSP-Sprinkler Rough-in11/1/201011/2/201011/2/2010 11:53:08 AMAPASS
The underground supply piping is ok to cover.
FIR10-00339 INSP-Final Inspection11/1/201011/2/201011/2/2010 11:48:53 AMAFAIL
The inspector's test has not been set up to verify note "B" of the review comments. (two heads for 7 minutes). All other items appear ok.
BLD10-01509 FIRE-Final Inspection11/1/201011/2/201011/2/2010 11:00:36 AMAFAIL
Provide inspection/final on the project related fire alarm permit and repair the exit sign out of the back office area and provide an emergency light in the warehouse area.
BLD08-01439 FIRE-Final Inspection11/1/201011/2/201011/2/2010 10:58:19 AMAPASS
Life safety passed. Matt is repairing the exit sign at the main exit prior to the building inspection.
FIR10-00498 INSP-Final Inspection10/29/201011/2/201011/2/2010 10:39:56 AMAFAIL
Relocate the two smoke detectors in the warehouse to the deck. Relocate three smoke detectors in the office area away from the supply registers. No testing was performed. As builts need to be provided showing the 12 guage wire used in the notification circuit and the correction of the plan reviewers redline comments.
FIR10-00028 INSP-Sprinkler Rough-in11/1/201011/2/201011/2/2010 9:39:35 AMAPASS
24 hr air test inspection started at 9:30 am with 46psi on the guage.