FIR09-00077
| INSP-Final Inspection | 11/2/2010 | 11/2/2010 | 11/2/2010 3:33:23 PM | P | CANC |
|
|
Cancelled due to time constraints and Guy and my schedule not matching. Guy is rescheduling for first thing in the morning.
|
FIR09-00012
| INSP-Final Inspection | 11/2/2010 | 11/2/2010 | 11/2/2010 3:32:55 PM | P | CANC |
|
|
Cancelled due to time constraints and Guy and my schedule not matching. Guy is rescheduling for first thing in the morning.
|
FIR09-00174
| INSP-Final Inspection | 11/2/2010 | 11/2/2010 | 11/2/2010 3:32:18 PM | P | CANC |
|
|
Cancelled due to time constraints and Guy and my schedule not matching. Guy is rescheduling for first thing in the morning.
|
FIR10-00522
| INSP-Sprinkler Rough-in | 11/2/2010 | 11/2/2010 | 11/2/2010 3:30:44 PM | P | PASS |
|
|
The sprinkler piping is ok to cover.
|
BLD10-02100
| FIRE-Final Inspection | 11/1/2010 | 11/2/2010 | 11/2/2010 2:48:09 PM | A | FAIL |
|
|
Provide annual inspection for all fire extinguishers, provide exit discharge lights at the three exits, provide correct remote annunciators or meet the exception of IMC 606.2
|
BLD10-02101
| FIRE-Final Inspection | 11/1/2010 | 11/2/2010 | 11/2/2010 2:45:14 PM | A | FAIL |
|
|
Provide annual inspection all of the fire extinguishers and repair or remove the exit sign.
|
FIR10-00489
| INSP-Final Inspection | 11/2/2010 | 11/2/2010 | 11/2/2010 1:35:28 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00400
| INSP-Sprinkler Rough-in | 11/1/2010 | 11/2/2010 | 11/2/2010 11:53:08 AM | A | PASS |
|
|
The underground supply piping is ok to cover.
|
FIR10-00339
| INSP-Final Inspection | 11/1/2010 | 11/2/2010 | 11/2/2010 11:48:53 AM | A | FAIL |
|
|
The inspector's test has not been set up to verify note "B" of the review comments. (two heads for 7 minutes). All other items appear ok.
|
BLD10-01509
| FIRE-Final Inspection | 11/1/2010 | 11/2/2010 | 11/2/2010 11:00:36 AM | A | FAIL |
|
|
Provide inspection/final on the project related fire alarm permit and repair the exit sign out of the back office area and provide an emergency light in the warehouse area.
|
BLD08-01439
| FIRE-Final Inspection | 11/1/2010 | 11/2/2010 | 11/2/2010 10:58:19 AM | A | PASS |
|
|
Life safety passed. Matt is repairing the exit sign at the main exit prior to the building inspection.
|
FIR10-00498
| INSP-Final Inspection | 10/29/2010 | 11/2/2010 | 11/2/2010 10:39:56 AM | A | FAIL |
|
|
Relocate the two smoke detectors in the warehouse to the deck. Relocate three smoke detectors in the office area away from the supply registers. No testing was performed. As builts need to be provided showing the 12 guage wire used in the notification circuit and the correction of the plan reviewers redline comments.
|
FIR10-00028
| INSP-Sprinkler Rough-in | 11/1/2010 | 11/2/2010 | 11/2/2010 9:39:35 AM | A | PASS |
|
|
24 hr air test inspection started at 9:30 am with 46psi on the guage.
|