FIR16-00694
| INSP-Sprinkler Rough-in | 11/1/2016 | 11/2/2016 | 11/2/2016 3:19:28 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR15-00683
| INSP-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 3:17:05 PM | P | PASS |
|
|
permit finaled
|
BLD16-03934
| FIRE-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 2:39:23 PM | P | CANC |
|
|
Not ready for a final yet due to cordination with contractor to perform the smoke evac. test. Bill Phone #: ###-####
|
FIR16-00528
| INSP-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 2:30:57 PM | P | PASS |
|
|
Permit finaled
|
FIR16-00495
| INSP-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 2:03:23 PM | P | PASS |
|
|
Permit finaled
|
FIR16-00455
| INSP-Sprinkler Rough-in/Hydro | 11/2/2016 | 11/2/2016 | 11/2/2016 2:01:39 PM | P | FAIL |
|
|
Underground hydro test failed because when I came back to verify pressure some one had removed the guage. So no test was performed.
|
FIR16-00640
| INSP-Sprinkler Rough-in/Hydro | 11/1/2016 | 11/2/2016 | 11/2/2016 2:00:42 PM | A | PART |
|
|
Rough-in passed for the most part except ron stated that he is going to install 401 canopies on the second floor due to light fixture obstructions and the electrician is going to move the lights 3' away on the first floor. So another rough-in will be needed and another hydro test for the overhead system. Pipe sizing and hangers are ok.
|
FIR16-00665
| INSP-Sprinkler Rough-in | 11/2/2016 | 11/2/2016 | 11/2/2016 1:23:41 PM | P | PART |
|
|
Underground supply piping is ok to cover except for the areas where thrust blocks need to be poured.
|
BLD16-03702
| FIRE-Final Inspection | 10/28/2016 | 11/2/2016 | 11/2/2016 12:42:45 PM | A | PASS |
|
|
Life safety passed. Revised floor plan was provided in an email from plan review. Correct hardware and sticker to be installed prior to a building inspection
|
FIR16-00440
| INSP-Sprinkler Rough-in/Hydro | 10/31/2016 | 11/2/2016 | 11/2/2016 12:15:13 PM | P | PASS |
|
|
Tenting passed. Piping can be covered.
|
BLD15-00890
| FIRE-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 11:27:13 AM | P | FAIL |
|
|
Still need the emergency light on the second floor northwest corner repaired. All other items have been corrected.
|
FIR16-00443
| INSP-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 10:37:40 AM | A | FAIL |
|
|
Needed an above ground hydro test which passed. Final to be rescheduled for tomorrow morning.
|
BLD15-01139
| FIRE-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 9:56:01 AM | A | PASS |
|
|
Life safety passed. Contractor to provide self luminous exit signs at the gates as per the building review note 10
|
BLD16-01107
| FIRE-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 9:02:04 AM | A | PASS |
|
|
Life safety passed
|
FIR16-00439
| INSP-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 9:01:44 AM | A | PASS |
|
|
Permit finaled
|