BLD16-03954
| FIRE-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 3:41:20 PM | P | PASS |
|
|
Previous items corrected. Life safety pass.
|
FIR16-00598
| INSP-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 3:28:57 PM | P | PASS |
|
|
System tested satisfactory. Scope of work complete, permit finaled.
|
FIR16-00578
| INSP-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 3:28:24 PM | P | PASS |
|
|
Scope of work complete. Permit Finaled.
|
BLD16-02810
| FIRE-Conference | 11/2/2016 | 11/2/2016 | 11/2/2016 3:28:06 PM | P | DONE |
|
|
Verify floor plan posted at panel with correct monitor modules identified for duct detectors.
|
NAF16-00023
| INSP-Sprinkler Rough-in/Hydro | 11/1/2016 | 11/2/2016 | 11/2/2016 12:08:07 PM | A | PASS |
|
|
Hydrostatic test on all three systems completed satisfactory. Remaining rough in areas completed satisfacory. Still Pending: -dry system 24 hr air test. - 2nd floor protector on upright - 2nd flr mechanical room spaced with 5' verify there is an obstruction to warrant - 2nd floor missing hangar at apartments
|
FIR15-00650
| INSP-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 11:02:16 AM | P | PASS |
|
|
Verified central monitoring station receiving signals, tested a trouble, alarm and supervisory.
Scope of work complete, permit finaled.
|
BLD16-03953
| FIRE-Final Inspection | 11/1/2016 | 11/2/2016 | 11/2/2016 9:16:24 AM | A | PASS |
|
|
Life safety pass. Permanent suite numbers are on order and with only two tenant spaces OK.
|