Inspections for the day of: Friday, November 2, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02181 Electrical Rough-In11/2/201811/2/201811/2/2018 3:18:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Bryan Atkins
Bathroom rough in ok cover
ELE18-04189 Electrical Rough-In11/2/201811/2/201811/2/2018 2:38:34 PMPPART
Walls inspection with exception to the South wall in conference room. Working on solution for floor outlet. Phone #: ###-#### Inspection requested via web by Dean Gernaat
Walls as noted rough in ok cover
ELE18-03016 Final11/2/201811/2/201811/2/2018 2:25:08 PMPPASS
This was the lighting control cabinet that we had to replace with a 2 meter pedestal. Ready for inspection. Phone #: ###-#### Inspection requested via web by Kelly Tarter Final ok
ELE18-03016 Permanent Service11/2/201811/2/201811/2/2018 2:24:51 PMPPASS
This was the lighting control cabinet that we had to replace with a 2 meter pedestal. Ready for inspection. Phone #: ###-#### Inspection requested via web by Kelly Tarter
Originally installed a single meter base pedistal, changed to 2 meter base pedistal. p/s u/g n ok
ELE18-04155 Electrical Rough-In11/2/201811/2/201811/2/2018 12:58:39 PMAPASS
Phone #: ###-#### Inspection requested via web by Mike R. Rossknecht
Replacing bathroom and kithen cabinets only, no new circuits. Rough in ok cover
ELE18-04220 Permanent Service11/1/201811/2/201811/2/2018 12:32:02 PMAPASS
Contact: Matt Cinko Phone #: ###-#### Inspection requested via web by Deb Gooden p/s o/h rec ok
ELE18-04217 Electrical Rough-In11/2/201811/2/201811/2/2018 12:18:29 PMAFAIL
Phone #: ###-#### Inspection requested via web by Tyler Ridley
110.3(A)- Boxes installed shall be listed. Allied pancake boxes provide listing or replace.
110.3(B)- Acorn clamp shall be installed as per manufacturers instructions. Grounding electrode conductor shall be installed opposite of set screw.
300.4- Several nail plates needed through out. Garage out lights, master bed corner, master hall, fire place left side, entry, pantry switch, utility. 334.12- NM cable shall not be installed where subject to physical damage. Utility switch leg out of wall below ceiling and pulled tight.
408.3(A)(2)- Barriers shall be in place where service conductors terminate in panel.
ELE18-03525 Electrical Rough-In11/1/201811/2/201811/2/2018 11:28:12 AMAPART
Wall inspection. Please call Cory if you have any questions ###-#### Phone #: ###-#### Inspection requested via web by Cyndi Dale
Discussed common grounding electrode system, and location of existing services no issue with locations.
Walls and hardlids east and south ends rough in ok cover.
ELE18-02369 Electrical Rough-In10/31/201811/2/201811/2/2018 10:29:11 AMAPASS
Please call Joey Campbell at ###-#### prior to arrival. 1st floor wall inspection. Phone #: ###-#### Inspection requested via web by Scott Campbell
Fire riser room, bathrooms, corridors and noted in orange on contractor print wall rough in ok cover