ELE18-02181
| Electrical Rough-In | 11/2/2018 | 11/2/2018 | 11/2/2018 3:18:44 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bryan Atkins Bathroom rough in ok cover
|
ELE18-04189
| Electrical Rough-In | 11/2/2018 | 11/2/2018 | 11/2/2018 2:38:34 PM | P | PART |
|
|
Walls inspection with exception to the South wall in conference room. Working on solution for floor outlet. Phone #: ###-#### Inspection requested via web by Dean Gernaat Walls as noted rough in ok cover
|
ELE18-03016
| Final | 11/2/2018 | 11/2/2018 | 11/2/2018 2:25:08 PM | P | PASS |
|
|
This was the lighting control cabinet that we had to replace with a 2 meter pedestal. Ready for inspection. Phone #: ###-#### Inspection requested via web by Kelly Tarter Final ok
|
ELE18-03016
| Permanent Service | 11/2/2018 | 11/2/2018 | 11/2/2018 2:24:51 PM | P | PASS |
|
|
This was the lighting control cabinet that we had to replace with a 2 meter pedestal. Ready for inspection. Phone #: ###-#### Inspection requested via web by Kelly Tarter Originally installed a single meter base pedistal, changed to 2 meter base pedistal. p/s u/g n ok
|
ELE18-04155
| Electrical Rough-In | 11/2/2018 | 11/2/2018 | 11/2/2018 12:58:39 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mike R. Rossknecht Replacing bathroom and kithen cabinets only, no new circuits. Rough in ok cover
|
ELE18-04220
| Permanent Service | 11/1/2018 | 11/2/2018 | 11/2/2018 12:32:02 PM | A | PASS |
|
|
Contact: Matt Cinko Phone #: ###-#### Inspection requested via web by Deb Gooden p/s o/h rec ok
|
ELE18-04217
| Electrical Rough-In | 11/2/2018 | 11/2/2018 | 11/2/2018 12:18:29 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 110.3(A)- Boxes installed shall be listed. Allied pancake boxes provide listing or replace. 110.3(B)- Acorn clamp shall be installed as per manufacturers instructions. Grounding electrode conductor shall be installed opposite of set screw. 300.4- Several nail plates needed through out. Garage out lights, master bed corner, master hall, fire place left side, entry, pantry switch, utility. 334.12- NM cable shall not be installed where subject to physical damage. Utility switch leg out of wall below ceiling and pulled tight. 408.3(A)(2)- Barriers shall be in place where service conductors terminate in panel.
|
ELE18-03525
| Electrical Rough-In | 11/1/2018 | 11/2/2018 | 11/2/2018 11:28:12 AM | A | PART |
|
|
Wall inspection. Please call Cory if you have any questions ###-#### Phone #: ###-#### Inspection requested via web by Cyndi Dale Discussed common grounding electrode system, and location of existing services no issue with locations. Walls and hardlids east and south ends rough in ok cover.
|
ELE18-02369
| Electrical Rough-In | 10/31/2018 | 11/2/2018 | 11/2/2018 10:29:11 AM | A | PASS |
|
|
Please call Joey Campbell at ###-#### prior to arrival. 1st floor wall inspection. Phone #: ###-#### Inspection requested via web by Scott Campbell Fire riser room, bathrooms, corridors and noted in orange on contractor print wall rough in ok cover
|