Inspections for the day of: Friday, November 2, 2018.
Number of inspections: 27
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04200 Temporary Service11/1/201811/2/201811/2/2018 3:30:11 PMPFAIL
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04201 Temporary Service11/1/201811/2/201811/2/2018 3:29:50 PMPFAIL
Temp Power for Building B
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04203 Temporary Service11/1/201811/2/201811/2/2018 3:29:17 PMPFAIL
Temp Power Inspection for Building C
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04209 Temporary Service11/1/201811/2/201811/2/2018 3:28:45 PMPFAIL
Temp Service inspection for Building K
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04208 Temporary Service11/1/201811/2/201811/2/2018 3:28:00 PMPFAIL
Temp Power inspection for Building J
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04207 Temporary Service11/1/201811/2/201811/2/2018 3:27:13 PMPFAIL
Temp Power inspection for Building H
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04206 Temporary Service11/1/201811/2/201811/2/2018 3:26:39 PMPFAIL
Temp Power inspection for Building G
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04205 Temporary Service11/1/201811/2/201811/2/2018 3:25:41 PMPFAIL
Temp Power for Building E
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04204 Temporary Service11/1/201811/2/201811/2/2018 3:25:06 PMPFAIL
Temp Service inspection for Building D
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04210 Temporary Service11/1/201811/2/201811/2/2018 3:24:42 PMPFAIL
Temp Service inspection for the Clubhouse
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek 590.6B1 GFCI protection shall be provided for all temp receps(All 50A cord drops) 406.9A All receps in wet locations shall be type WR( All temp GFCI recep)
ELE18-04224 Electrical Rough-In11/2/201811/2/201811/2/2018 2:31:15 PMPPASS
lower unit vacant, front door unlocked. I should be there. Thank You!! Phone #: ###-#### Inspection requested via web by Robert Schroder rough in ok
ELE18-04143 Conference11/2/201811/2/201811/2/2018 2:09:36 PMPPASS
Also called in for a temporary power today, so I need to know in advance I''m working in Meridian... Phone #: ###-#### Inspection requested via web by Rick Beckman Talked about using exhisting service for temp power
ELE18-04143 Temporary Service11/2/201811/2/201811/2/2018 2:06:18 PMPPASS
Also called in for a conference today, so I need to know in advance I''m working in Meridian... Phone #: ###-#### Inspection requested via web by Rick Beckman t/s u/g rec ok
ELE18-01206 Electrical Rough-In11/2/201811/2/201811/2/2018 1:22:55 PMPPASS
Please call Bryant for wall and ceiling hard lid inspections on 1st and 2nd floor.
Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo Walls only Shaft walls ok to cover
ELE18-02713 Final11/2/201811/2/201811/2/2018 1:22:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson Corrections made final ok
ELE18-03808 Rough-In Permanent Service11/2/201811/2/201811/2/2018 1:15:24 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
ELE18-04213 Electrical Rough-In11/1/201811/2/201811/2/2018 1:01:06 PMPPASS
Under ground for floor plug and island Phone #: ###-#### Inspection requested via web by Zane Robertson Underground only ok to cover
ELE18-03879 Electrical Rough-In11/1/201811/2/201811/2/2018 12:50:46 PMPPASS
send message 15 minutes before arrival to allow me to leave work and be there on time Phone #: ###-#### Inspection requested via web by Douglas Hughes Sunroom ok to cover
ELE18-04193 Conference11/1/201811/2/201811/2/2018 12:21:15 PMAPASS
Andy (Husband is who you''ll meet) Phone #: ###-#### Installing a factory wired tranfer switch to external plug. Discussed when to call for inspection
ELE18-04158 Electrical Rough-In11/1/201811/2/201811/2/2018 12:09:28 PMAPASS
Will call first thing in morning and schedule a time to meet you onsite. Phone #: ###-#### Inspection requested via web by Jesse Simpson Final ok
ELE18-04064 Final10/31/201811/2/201811/2/2018 11:55:46 AMAPASS
Morgan Phone #: ###-#### Elevator electrical only final ok
ELE18-04219 Electrical Rough-In11/1/201811/2/201811/2/2018 11:41:00 AMAPASS
Bonding inspection any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller corner bond only ok
ELE18-03068 Final11/1/201811/2/201811/2/2018 11:30:53 AMAPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE18-02559 Electrical Rough-In11/2/201811/2/201811/2/2018 10:56:33 AMAFAIL
Please call Toby for hard lid ceiling inspection at B36 in the servery area. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo 314.29. Junction boxes shall be accessible(4 seperate locations in hard lid area)
ELE17-02880 Final11/1/201811/2/201811/2/2018 9:55:48 AMAPART
This is a partial final. Contact is Rene Ramakers. Phone #: ###-#### Inspection requested via web by Scott Campbell Temp final ok List of corrections left With Tony.
ELE18-04083 Electrical Rough-In11/1/201811/2/201811/2/2018 8:40:36 AMAPASS
Inspect underground trench so it can be backfilled at Bldg. 80 Phone #: ###-#### Inspection requested via web by Steve Moss Underground for 2 new parking lot lights only ok to cover
ELE18-03873 Electrical Rough-In11/1/201811/2/201811/2/2018 8:26:13 AMAPASS
call when get there // UG r/i // Jose Phone #: ###-#### Underground for parking lot lighting only ok to cover