ELE02-03444
| Final | 11/19/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | A | PASS |
|
|
###-####
P/S U/G N Ok 11/20/2002 9:22:48 AM
|
ELE02-03444
| Final | 11/19/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | A | PASS |
|
|
###-####
P/S U/G N Ok 11/20/2002 9:22:48 AM
|
ELE02-02077
| Final | 11/19/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | A | PASS |
|
|
PUMP ON COUNTER-GENE ###-####-RE-INSP
|
ELE02-03560
| Temporary Service | 11/19/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/19/2002 at 22:17:20. Contact: ###-####.
T/S O/H Ok 11/20/2002 8:53:26 AM
|
ELE02-03609
| Rough-In Permanent Service | 11/20/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | P | FAIL |
|
|
###-#### -bill
314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies.
Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.
Upstairs
250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes.
(B) Nonmetallic Boxes. One or more equipment grounding conductors brought into a nonmetallic outlet box shall be arranged so that a connection can be made to any fitting or device in that box requiring grounding.
210.52 Dwelling Unit Receptacle Outlets.
This section provides requirements for 125-volt, 15- and 20-ampere receptacle outlets.
2 Upstairs and change location of broken box by large slider.
11/20/2002 2:31:06 PM
|
ELE02-03579
| Temporary Service | 11/20/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | P | PASS |
|
|
VIVIAN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
T/S U/G Ok 11/20/2002 2:28:39 PM
|
ELE02-03554
| Electrical Rough-In | 11/20/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/20/2002 at 08:50:47. Contact: ###-####.
314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies.
Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.
11/20/2002 12:58:40 PM
|
ELE02-03145
| Final | 11/20/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | P | PASS |
|
|
###-#### ANETTA
|
ELE02-03554
| Permanent Service | 11/20/2002 | 11/20/2002 | 11/20/2002 12:00:00 AM | P | PASS |
|
|
P/S U/G N Ok
|