Inspections for the day of: Wednesday, November 20, 2002.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00372 INSP-Final Inspection11/19/200211/20/200211/20/2002 12:00:00 AMAFAIL
provide mechanical plans, provide additional duct smoke detectors as required and resubmit plans for review, duct detectors did not shut down the hvac units as required, remove all non functioning fire alarm devices (old system), and relocate the manual pull stations as per the review comments.. NO OTHER ITEMS VERIFIED OR TESTED 11/20/2002 11:11:31 AM
FIR02-00434 INSP-Final Inspection11/19/200211/20/200211/20/2002 12:00:00 AMAFAIL
can't give final until the ceiling tile is installed but the sprinkler piping can be covered 11/20/2002 9:03:13 AM
FIR02-00407 INSP-Sprinkler Rough-in/Hydro11/19/200211/20/200211/20/2002 12:00:00 AMAPASS
rough-in for the inrack sprinklers is ok, but they are not tied into the riser yet. The hydro test is ok. The wrong sprinkler heads have been installed and require changed or reapproved. The hose valve connection is incorrect 11/20/2002 3:59:00 PM
BLD02-02453 FIRE-Final Inspection11/19/200211/20/200211/20/2002 12:00:00 AMAFAIL
provide approved door hardware on the main exit and provide duct smoke detectors for hvac shutdown. 11/20/2002 3:54:52 PM
BLD02-02453 FIRE-Final Inspection11/19/200211/20/200211/20/2002 12:00:00 AMAFAIL
provide approved door hardware on the main exit and provide duct smoke detectors for hvac shutdown. 11/20/2002 3:54:52 PM