FIR03-00263
| INSP-Alarm Testing | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | A | FAIL |
|
|
Wes; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need 177cd strobe in ADA room as the strobe is within 24 inches of ceiling; need lockout on FACP circuit breaker; need map; need sign on fire alarm panel cosmetic door; need to test sprinkler flow; all other alarm items have been tested 11/20/2003 11:23:02 AM
|
BLD03-01476
| FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | A | PASS |
|
|
Jerry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD03-02103
| FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | A | FAIL |
|
|
Earl; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes emergency light still not working 11/20/2003 10:01:54 AM
|
FIR03-00373
| INSP-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | A | NR |
|
|
###-#### Mark received call from contractor that this will have to be rescheduled 11/20/2003 7:17:28 AM
|
BLD02-02976
| FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | A | FAIL |
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need aapproved plans for review; obtain permit for fire sprinkler added to cooler 11/20/2003 9:41:45 AM
|
BLD03-01474
| FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | A | PART |
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie per Dave Miller fire/life safety will be on a temp occupancy pending approval/testing of the fire alarm system 11/20/2003 8:49:05 AM
|
BLD03-02104
| FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/19/2003 at 12:11:25 PM. Contact: ###-####.
|
FIR03-00371
| INSP-Final Inspection | 11/18/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PASS |
|
|
Needs to be after school hours preferably @4:00pm please call to verify; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
BLD03-01381
| FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PASS |
|
|
Earl; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
FIR03-00592
| INSP-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/19/2003 at 10:41:52 AM. Contact: ###-####.
|
FIR03-00557
| INSP-Sprinkler Rough-in/Hydro | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 11/19/2003 at 10:45:14 AM. Contact: ###-####. need heads at top of stair; two flow switches will need separate zones for alarm monitoring 11/20/2003 3:32:15 PM
|
FIR03-00562
| INSP-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | CANC |
|
|
Rick
The items you addressed yesterday have been corrected. We would like to reschedule a new inspection. Please call me at the office at ###-#### or my cell at ###-####
Thanks
Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick double inspection entry 11/20/2003 11:54:46 AM
|
BLD03-01119
| FIRE-Final Inspection | 11/20/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | NR |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes rescheduled for 11/21 11/20/2003 2:58:28 PM
|
BLD03-01732
| FIRE-Final Inspection | 11/20/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/20/2003 at 9:09:21 AM. Contact: ###-####. need to clarify with the city about how to proceed with the exsisting alarm system - upgrade or remove from this TI space 11/20/2003 5:18:41 PM
|
BLD03-01894
| FIRE-Final Inspection | 11/20/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PASS |
|
|
|
BLD03-00688
| FIRE-Final Inspection | 11/20/2003 | 11/20/2003 | 11/20/2003 12:00:00 AM | P | PASS |
|
|
|