ELE06-04334
| Final | 11/20/2006 | 11/20/2006 | 11/20/2006 4:20:51 PM | P | PASS |
|
|
ok to final
|
ELE06-04334
| Electrical Rough-In | 11/20/2006 | 11/20/2006 | 11/20/2006 4:17:49 PM | P | PASS |
|
|
We installed and wired a new exterior wallpak light above the garage door in the alley and fed it from the garage door opener receptacle. Tech/Dan/###-####.(6111103ib).Thanks!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok
|
ELE06-03714
| Electrical Rough-In | 11/17/2006 | 11/20/2006 | 11/20/2006 4:01:56 PM | P | FAIL |
|
|
Matt ###-#### met owner, left corr notice,nec 300.4 (A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,250.86 metal boxes shall be grounded, 110.12(C) there shall be no broken parts, 210.52(A)(1) recpt shall be spaced such thay no point is over 6' from an outlet, 210.12(B) AFCI shall be provided for bedroom circuit outlets, lights and power,334.24 nm cable bend radius shall be 5 times diameter, BCC all make-up shall be done
|
ELE06-03275
| Final | 11/20/2006 | 11/20/2006 | 11/20/2006 3:55:39 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 11/20/2006 at 7:02:47 AM. Contact: ###-####. met contr, left corr notice,signed t/o card, nec 110.3(B) and BCC 4-05-33(A)(B) all electric equipment shall be listed by a nationally recognized testing laboratory (boiler), Note; correction shall be made within 2 weeks or further action will be taken, such as removal of power
|
ELE06-04118
| Electrical Rough-In | 11/20/2006 | 11/20/2006 | 11/20/2006 3:16:59 PM | P | PART |
|
|
darrell - ceiling cover - 2nd floor - n/s hallway ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 2nd fl west hall ok to cover
|
ELE06-03371
| Final | 11/20/2006 | 11/20/2006 | 11/20/2006 2:58:41 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/20/2006 at 7:34:39 AM. Contact: ###-####. ok to final
|
ELE06-02560
| Final | 11/20/2006 | 11/20/2006 | 11/20/2006 2:44:09 PM | P | PASS |
|
|
skip ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-04330
| Temporary Service | 11/20/2006 | 11/20/2006 | 11/20/2006 1:04:39 PM | P | FAIL |
|
|
Internet Inspection Request from: Rowdy Monroe contr called elect, nec 110.26(A) (1) depth of work space shall be 36" by 30" wide, 110.12(C) there shall be no broken parts, gec
|
ELE05-00855
| ELE-Aging Inspection | 11/20/2006 | 11/20/2006 | 11/20/2006 11:01:03 AM | | DONE |
|
|
suc
|
ELE06-04318
| Temporary Service | 11/17/2006 | 11/20/2006 | 11/20/2006 10:08:24 AM | A | PASS |
|
|
###-#### stan called, left survey, nec 312.5 all conductors entering enclosures shall have abrasion protection,110.3(B) only listed breakers per panel mfgr shall be installed t/s u/g n ok
|
ELE06-04321
| Electrical Rough-In | 11/17/2006 | 11/20/2006 | 11/20/2006 9:36:02 AM | A | PART |
|
|
gene; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to cover attic floor
|
ELE06-03542
| Final | 11/17/2006 | 11/20/2006 | 11/20/2006 9:35:26 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final
|
ELE06-03541
| Final | 11/17/2006 | 11/20/2006 | 11/20/2006 9:35:05 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final
|
ELE06-03935
| Rough-In Permanent Service | 11/20/2006 | 11/20/2006 | 11/20/2006 9:08:23 AM | A | FAIL |
|
|
Internet Inspection Request from: Cevyn Recla called, left corr notice, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 box shall be flush in combustible walls, 250.86 shall ground metal boxes, 334.30 se cable shall be secured within 12" of box, 300.15 all cable shall terminate in boxes, 110.26 work space shall be provided about electrical equipment (service), BCC all make-up shall be done
|
ELE06-04069
| Final | 11/17/2006 | 11/20/2006 | 11/20/2006 8:28:08 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung told contr, left corr notice, nec 110.26(F)(1) there shall be no foreign piping over panel dedicated space, 330.30(B) mc cable shall be strapped within 12" of box,358.30(A) emt shall be secured every 10' and within 3' of box, 300.15 mc cable shall term in box,BCC no violations shall be retained
|
ELE06-04309
| Electrical Rough-In | 11/20/2006 | 11/20/2006 | 11/20/2006 7:46:35 AM | P | CANC |
|
|
Contact: Eric Cobiskey; Phone #: ###-#### Internet Inspection Request from: Deb McCoy Inspection cancelled from web by: Deb McCoy
|