Inspections for the day of: Monday, November 20, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04334 Final11/20/200611/20/200611/20/2006 4:20:51 PMPPASS
ok to final
ELE06-04334 Electrical Rough-In11/20/200611/20/200611/20/2006 4:17:49 PMPPASS
We installed and wired a new exterior wallpak light above the garage door in the alley and fed it from the garage door opener receptacle. Tech/Dan/###-####.(6111103ib).Thanks!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok
ELE06-03714 Electrical Rough-In11/17/200611/20/200611/20/2006 4:01:56 PMPFAIL
Matt ###-#### met owner, left corr notice,nec 300.4 (A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,250.86 metal boxes shall be grounded, 110.12(C) there shall be no broken parts, 210.52(A)(1) recpt shall be spaced such thay no point is over 6' from an outlet, 210.12(B) AFCI shall be provided for bedroom circuit outlets, lights and power,334.24 nm cable bend radius shall be 5 times diameter, BCC all make-up shall be done
ELE06-03275 Final11/20/200611/20/200611/20/2006 3:55:39 PMPPART
Scheduled by a contractor via Hello! on 11/20/2006 at 7:02:47 AM. Contact: ###-####. met contr, left corr notice,signed t/o card, nec 110.3(B) and BCC 4-05-33(A)(B) all electric equipment shall be listed by a nationally recognized testing laboratory (boiler), Note; correction shall be made within 2 weeks or further action will be taken, such as removal of power
ELE06-04118 Electrical Rough-In11/20/200611/20/200611/20/2006 3:16:59 PMPPART
darrell - ceiling cover - 2nd floor - n/s hallway ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 2nd fl west hall ok to cover
ELE06-03371 Final11/20/200611/20/200611/20/2006 2:58:41 PMPPASS
Scheduled by a contractor via Hello! on 11/20/2006 at 7:34:39 AM. Contact: ###-####. ok to final
ELE06-02560 Final11/20/200611/20/200611/20/2006 2:44:09 PMPPASS
skip ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-04330 Temporary Service11/20/200611/20/200611/20/2006 1:04:39 PMPFAIL
Internet Inspection Request from: Rowdy Monroe contr called elect, nec 110.26(A) (1) depth of work space shall be 36" by 30" wide, 110.12(C) there shall be no broken parts, gec
ELE05-00855 ELE-Aging Inspection11/20/200611/20/200611/20/2006 11:01:03 AM DONE
suc
ELE06-04318 Temporary Service11/17/200611/20/200611/20/2006 10:08:24 AMAPASS
###-#### stan called, left survey, nec 312.5 all conductors entering enclosures shall have abrasion protection,110.3(B) only listed breakers per panel mfgr shall be installed t/s u/g n ok
ELE06-04321 Electrical Rough-In11/17/200611/20/200611/20/2006 9:36:02 AMAPART
gene; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to cover attic floor
ELE06-03542 Final11/17/200611/20/200611/20/2006 9:35:26 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final
ELE06-03541 Final11/17/200611/20/200611/20/2006 9:35:05 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok to final
ELE06-03935 Rough-In Permanent Service11/20/200611/20/200611/20/2006 9:08:23 AMAFAIL
Internet Inspection Request from: Cevyn Recla called, left corr notice, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 box shall be flush in combustible walls, 250.86 shall ground metal boxes, 334.30 se cable shall be secured within 12" of box, 300.15 all cable shall terminate in boxes, 110.26 work space shall be provided about electrical equipment (service), BCC all make-up shall be done
ELE06-04069 Final11/17/200611/20/200611/20/2006 8:28:08 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung told contr, left corr notice, nec 110.26(F)(1) there shall be no foreign piping over panel dedicated space, 330.30(B) mc cable shall be strapped within 12" of box,358.30(A) emt shall be secured every 10' and within 3' of box, 300.15 mc cable shall term in box,BCC no violations shall be retained
ELE06-04309 Electrical Rough-In11/20/200611/20/200611/20/2006 7:46:35 AMPCANC
Contact: Eric Cobiskey; Phone #: ###-#### Internet Inspection Request from: Deb McCoy Inspection cancelled from web by: Deb McCoy