FIR05-00536
| INSP-Sprinkler Rough-in | 11/20/2006 | 11/20/2006 | 11/20/2006 4:20:18 PM | P | PASS |
|
|
See city approved plans for locations/rooms where piping is ok to cover.
|
FIR06-00752
| INSP-Sprinkler Rough-in | 11/20/2006 | 11/20/2006 | 11/20/2006 4:19:46 PM | P | PART |
|
|
Sprinkler piping is ok to cover in all areas except for MRI room, equipment room and dressing room.
|
FIR06-00807
| INSP-Final Inspection | 11/20/2006 | 11/20/2006 | 11/20/2006 4:18:21 PM | P | PASS |
|
|
permit finaled
|
BLD06-02684
| FIRE-Final Inspection | 11/17/2006 | 11/20/2006 | 11/20/2006 2:16:43 PM | A | FAIL |
|
|
Repair the rear double exit doors and repair the front exit sign/emergency light.
|
BLD06-02572
| FIRE-Final Inspection | 11/17/2006 | 11/20/2006 | 11/20/2006 1:48:45 PM | A | FAIL |
|
|
The smoke evac systems need tested and the new duct smoke detectors are not programed in yet and therefore could not be tested.
|
FIR06-00835
| INSP-Final Inspection | 11/17/2006 | 11/20/2006 | 11/20/2006 1:46:42 PM | P | FAIL |
|
|
Did not test the systems because not all of the lights were operating on the main hood so I could not verify electrical shutoff. Also both fryers do not meet the 4' rule of outer lip of hood to the cooking surface as stated in the IMC. Also need signs for the manual pull stations.
|
BLD06-02890
| FIRE-Final Inspection | 11/20/2006 | 11/20/2006 | 11/20/2006 12:23:10 PM | P | FAIL |
|
|
Provide door hardware, no manual flush bolts at the double office doors, test exit signs and emergency lights and provide a fire alarm permit for the duct detector tie in to the existing, but new fire alarm system.
|
BLD06-02191
| FIRE-Final Inspection | 11/17/2006 | 11/20/2006 | 11/20/2006 11:50:30 AM | A | PASS |
|
|
Life safety finaled
|
MIS06-00312
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:54:18 AM | A | PASS |
|
|
life safety finaled
|
MIS06-00307
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:54:04 AM | A | PASS |
|
|
life safety finaled
|
MIS06-00310
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:53:50 AM | A | PASS |
|
|
life safety finaled
|
MIS06-00309
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:53:37 AM | A | PASS |
|
|
life safety finaled
|
MIS06-00313
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:53:20 AM | A | PASS |
|
|
Life safety finaled
|
MIS06-00311
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:53:05 AM | A | PASS |
|
|
Life safety finaled
|
MIS06-00308
| FIR-Conference | 11/17/2006 | 11/20/2006 | 11/20/2006 10:52:47 AM | A | CANC |
|
|
Wrong inspection type called in.
|
MIS06-00308
| FIR-Final | 11/20/2006 | 11/20/2006 | 11/20/2006 10:50:33 AM | P | PASS |
|
|
life safety finaled
|
MIS06-00299
| FIR-Final | 11/17/2006 | 11/20/2006 | 11/20/2006 10:50:01 AM | A | PASS |
|
|
Life safety finaled
|
FIR06-00564
| INSP-Sprinkler Rough-in/Hydro | 11/20/2006 | 11/20/2006 | 11/20/2006 10:13:08 AM | A | PASS |
|
|
dry system is ok to cover. The single head in the overbuild area needs relocated. See approved plans for location
|