FIR07-00129
| INSP-Alarm Testing | 11/19/2007 | 11/20/2007 | 11/20/2007 5:48:34 PM | A | PART |
|
|
Begin fire alarm testing today including all related elevator control devices, FACP, batteries, phone lines, smoke at panel,FJ and initiation and detection devices for the 1st thru 3rd floors not including sprinkler monitoring tested today. Noted some device address changes, three deleted ID detectors, one pull station at the NW exit is still too high, need to provide a clean set of as-builts for field modifications and a current map at the panel.
|
FIR06-00504
| INSP-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 5:37:02 PM | P | NR |
|
|
|
FIR07-00235
| INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/20/2007 | 11/20/2007 5:36:20 PM | P | PART |
|
|
UG fire supply line hydrostatic test passed.
|
FIR07-00236
| INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/20/2007 | 11/20/2007 5:35:43 PM | P | PART |
|
|
UG fire supply line hydrostatic test passed.
|
FIR07-00234
| INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/20/2007 | 11/20/2007 5:34:59 PM | A | PART |
|
|
UG fire supply line hydrostatic test passed.
|
FIR07-00233
| INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/20/2007 | 11/20/2007 5:33:57 PM | A | PART |
|
|
UG supply line hydro test passed.
|
FIR07-00894
| INSP-Sprinkler Rough-in | 11/19/2007 | 11/20/2007 | 11/20/2007 2:25:09 PM | P | PART |
|
|
UG fire supply line is approved for cover, the hydrant at the street appears to be supplied by a dedicated line and is installed separate from the automatic sprinkler system supply per the general contractor.
|
BLD07-00754
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 1:13:54 PM | A | FAIL |
|
|
Need to repair one exit sign, provide additonal exit sign as discussed, remove door stop at the exit door to the waiting area, door swing at the first floor exit to the north stairway landing needs to be installed per approved plans.
|
FIR07-00932
| INSP-Sprinkler Rough-in | 11/19/2007 | 11/20/2007 | 11/20/2007 11:52:02 AM | A | FAIL |
|
|
UG fire supply line Install appears satisfactory, however no approved plans were left on site for verification of compliance with submitted plans.
|
FIR06-00584
| INSP-Final Inspection | 11/20/2007 | 11/20/2007 | 11/20/2007 11:09:55 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD05-02148
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 11:07:18 AM | A | NR |
|
|
Need project related fire sprinkler permit FIR06-00438 finaled prior to life safety final, need approved plans and review notes on site for verification of compliance at next site visit.
|
FIR06-00998
| INSP-Alarm Testing | 11/15/2007 | 11/20/2007 | 11/20/2007 11:05:03 AM | A | CANC |
|
|
Overbooked.
|
BLD07-02726
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 11:04:34 AM | A | PASS |
|
|
Life safety inspection passed.
|
FIR07-00467
| FIR-Aging Inspection | 11/20/2007 | 11/20/2007 | 11/20/2007 10:11:44 AM | | DEFR |
|
|
Work in progress.
|