FIR07-00739
| INSP-Sprinkler Rough-in/Hydro | 11/20/2007 | 11/20/2007 | 11/21/2007 8:45:09 AM | P | PASS |
|
|
Need backflow certified, hydro test completed and the forward flush performed. Also need the fire alarm interconnections tested.
|
BLD07-02974
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 3:23:17 PM | P | PART |
|
|
A temporary occupancy was given until the exit signs/emergency lights are repaired.
|
FIR07-00820
| INSP-Final Inspection | 11/20/2007 | 11/20/2007 | 11/20/2007 3:21:47 PM | P | FAIL |
|
|
The zones as labeled on the plans do not match the zones as installed in the field. No as-builts have been provided. I notified the fire alarm contractor to install per the drawings or provide asbuilts.
|
FIR07-00517
| INSP-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 2:25:54 PM | P | FAIL |
|
|
Sprinkler pendants are blocked by light fixtures. Both overhead and underground piping need hydro tested. The underground needs flushed. All riser details need inspected. Alarm interconnections need to be tested.
|
BLD07-02297
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 1:48:10 PM | A | FAIL |
|
|
The project related fire alarm permit needs finaled first.
|
FIR07-00919
| INSP-Alarm Testing | 11/19/2007 | 11/20/2007 | 11/20/2007 11:59:51 AM | A | FAIL |
|
|
The horns were not sync'd. The strobe operated correctly.
|
BLD07-01451
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 11:40:52 AM | A | FAIL |
|
|
Provide additional emergency lighting as discussed.
|
MIS07-00048
| FIR-Final | 11/19/2007 | 11/20/2007 | 11/20/2007 10:19:36 AM | A | PASS |
|
|
life safety passed.
|
FIR07-00594
| INSP-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 10:18:03 AM | A | PASS |
|
|
permit finaled
|
FIR07-00640
| INSP-Final Inspection | 11/16/2007 | 11/20/2007 | 11/20/2007 9:04:14 AM | A | FAIL |
|
|
The electrician stated that his office had contacted mike timmerman and it was ok to provide as-builts for the devices in the added corridor. I called to verify this with mike and he stated he could not recall any such conversation. The corridor appears to be an addition to the scope of work and should be resubmitted. No testing was performed since Ceicil with Kriezenbeck Const. did not want to have to disrupt the hospital twice for the fire alarm test.
|
BLD07-00948
| FIRE-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 8:54:42 AM | A | FAIL |
|
|
Still waiting to final the fire alarm permit then the life safety inspection can be started.
|
FIR07-00770
| INSP-Alarm Testing | 11/15/2007 | 11/20/2007 | 11/20/2007 7:53:16 AM | A | DONE |
|
|
The alarm at the garden center dry system has been repaired. The secondary phone line trouble restoral has been repaired. The audio/visual have been tested. Not all of the exterior tenant devices are operating. The audio/visual at the north east entrance is not operating. The a/v in the bakery needs relocated as per the plan. I need to spot check the high ceiling a/v's to verify candella compliance. The smoke detectors over the nac panels need located per code at the deck as discussed and tested. None of the duct smoke detectors were tested since the contractor did not have smoke. One hvac unit at the very west end of the store does not have a duct smoke detector as shown on the plans. The duct detectors in the outside tenants are not installed either. As-builts are required.
|