Inspections for the day of: Friday, November 20, 2009.
Number of inspections: 16
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00518 INSP-Conference11/13/200911/16/2009 P 
KEN Phone #: ###-#### (Follow up with Jerry McAdams)
FIR09-00656 INSP-Sprinkler Rough-in11/20/200911/20/200911/20/2009 3:27:52 PMPPASS
See the city approved plans for sprinkler piping above the hard lids that is ok to cover.
FIR09-00448 INSP-Sprinkler Rough-in/Hydro11/20/200911/20/200911/20/2009 2:50:32 PMPFAIL
Both of the overhead systems failed their hydro tests. I found three different locations where water was leaking out of the system and collecting in the baggies on the sprinkler pendants.
FIR09-00600 INSP-Sprinkler Rough-in/Hydro11/19/200911/20/200911/20/2009 2:49:09 PMAPART
I finished the rough-in inspection in the previously locked tenant space. I started the above ground hydro test but Brian called me later and stated that he had lost pressure and we would need to reschedule.
BLD09-00258 FIRE-Final Inspection11/20/200911/20/200911/20/2009 2:38:32 PMAPASS
life safety passed
BLD09-00251 FIRE-Final Inspection11/20/200911/20/200911/20/2009 2:38:02 PMAPASS
life safety passed
BLD09-00257 FIRE-Final Inspection11/20/200911/20/200911/20/2009 2:37:37 PMAPASS
life safety passed
BLD09-00254 FIRE-Final Inspection11/20/200911/20/200911/20/2009 2:37:20 PMAPASS
life safety passed
BLD09-00253 FIRE-Final Inspection11/19/200911/20/200911/20/2009 2:36:52 PMAPASS
life safety passed
BLD09-00255 FIRE-Final Inspection11/20/200911/20/200911/20/2009 2:36:26 PMAPASS
life safety passed
BLD09-00256 FIRE-Final Inspection11/20/200911/20/200911/20/2009 2:35:56 PMAPASS
life safety passed
BLD09-01919 FIRE-Final Inspection11/19/200911/20/200911/20/2009 11:33:25 AMAPART
A temporary occupancy is given with mark sentenos permission until the single action hardware is installed on the north exit door and the two overspaced sprinkler pendants.
BLD09-01819 FIRE-Final Inspection11/19/200911/20/200911/20/2009 8:17:16 AMACANC
Duplicate inspection
BLD09-01839 FIRE-Final Inspection11/19/200911/20/200911/20/2009 7:54:09 AMAPASS
Life safety passed
BLD09-01840 FIRE-Final Inspection11/19/200911/20/200911/20/2009 7:53:15 AMAPASS
Life safety passed.
FIR09-00616 INSP-Final Inspection11/20/200911/20/200911/20/2009 7:52:35 AMPPASS
Permit finaled