BLD12-02338
| FIRE-Final Inspection | 11/20/2012 | 11/20/2012 | 11/20/2012 3:43:10 PM | P | FAIL |
|
|
Inspection turned into a conference to address the need for a fire alarm permit for work that has already been performed.
|
BLD12-01915
| FIRE-Final Inspection | 11/19/2012 | 11/20/2012 | 11/20/2012 3:02:30 PM | A | CANC |
|
|
Rick Phone #: ###-####
|
FIR12-00288
| INSP-Final Inspection | 11/19/2012 | 11/20/2012 | 11/20/2012 3:01:13 PM | A | PASS |
|
|
Permit finaled
|
FIR12-00174
| INSP-Final Inspection | 11/19/2012 | 11/20/2012 | 11/20/2012 12:58:06 PM | A | PASS |
|
|
Permit finaled
|
BLD12-02782
| FIRE-Final Inspection | 11/19/2012 | 11/20/2012 | 11/20/2012 10:39:06 AM | A | FAIL |
|
|
All life safety items are ok except the floor plan needs to be resubmitted showing the actual wall layout. It appears some of this tenants area is now in the adjoining tenants area.
|
FIR12-00638
| INSP-Sprinkler Rough-in | 11/19/2012 | 11/20/2012 | 11/20/2012 10:10:57 AM | A | FAIL |
|
|
This was an ug to cover inspection which failed due to the piping not meeting the min. bury depth of 4'6".
|
FIR12-00645
| INSP-Final Inspection | 11/19/2012 | 11/20/2012 | 11/20/2012 10:09:38 AM | A | FAIL |
|
|
The zone 6 still did not report within the required 90 seconds. I then verified the actual time on a general alarm and found that it did not report to the monitoring station within the 90 seconds either. The fire alarm system shall meet current timing requirements as per NFPA 72. A re-inspection fee has been applied to this job for any more inspections.
|
FIR12-00416
| FIR-Aging Inspection | 11/20/2012 | 11/20/2012 | 11/20/2012 8:32:02 AM | | DEFR |
|
|
Need site inspection request
|
FIR12-00638
| INSP-Sprinkler Rough-in | 11/19/2012 | 11/20/2012 | 11/19/2012 2:49:55 PM | A | CANC |
|
|
This is an ug to cover. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|