Inspections for the day of: Wednesday, November 20, 2013.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01231 ELE-Aging Inspection11/20/201311/20/201311/22/2013 12:26:07 PM DONE
see final
ELE13-02737 Final11/20/201311/20/201311/21/2013 8:53:38 AMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
ELE13-03105 Electrical Rough-In11/19/201311/20/201311/20/2013 3:30:36 PMAPASS
Ufer ground inspection Phone #: ###-#### >> Inspection requested via web by Neil Adams rough-in ok cover Ufer grounding conductor
GCE13-00196 GCE-Temporary Service11/19/201311/20/201311/20/2013 3:26:22 PMAPASS
David ###-#### t/s u/g n ok
ELE13-03233 Permanent Service11/20/201311/20/201311/20/2013 2:39:44 PMPPASS
CINDY Phone #: ###-#### p/s u/g rec ok ETL listed hot tub on site
ELE13-02981 Final11/19/201311/20/201311/20/2013 2:19:24 PMANR
Door lock code: 2474. final for energize. Thank you, Lynn. Phone #: ###-#### >> Inspection requested via web by Lynn Solmon Not ready for final at this time, power not connected
ELE13-02981 Permanent Service11/20/201311/20/201311/20/2013 2:15:53 PMPPASS
Door lock code: 2474. final for energize. Thank you, Lynn. Phone #: ###-#### >> Inspection requested via web by Lynn Solmon p/s u/g n ok meter pack
ELE13-03212 Final11/20/201311/20/201311/20/2013 1:52:36 PMPPASS
Jim Gabriel Phone #: ###-#### final ok
ELE13-03207 Final11/20/201311/20/201311/20/2013 1:29:52 PMPFAIL
Jim Gabriel Phone #: ###-#### MC cable and EMT connected to contactor enclosures not secured and supported as required by NEC 330.30 and 358.30 NEC 408.4 circuit indentifcation NEC 408.7 Unused opening, KO plugs missing in control panel
ELE13-03257 Rough-In Permanent Service11/19/201311/20/201311/20/2013 12:09:46 PMPPASS
please call Bob with any problems. Thanks Daryl!! Phone #: ###-#### >> Inspection requested via web by Julie Schroder rough-in p/s u/g n ok
ELE12-00936 ELE-Aging Inspection11/20/201311/20/201311/20/2013 10:49:51 AM DONE
contractor will call for final
ELE13-02559 Electrical Rough-In11/19/201311/20/201311/20/2013 10:22:15 AMAPASS
site underground needs cover inspect call corey with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig rough-in ok service conduit trench
ELE13-03204 Permanent Service11/19/201311/20/201311/20/2013 10:14:22 AMAPASS
access code for door is 9217. Please call with any questions. Need ok for Idaho power to restore power. ONce power is restored we will come back and label panel. ###-#### Phone #: ###-#### >> Inspection requested via web by Randy Fletcher p/s u/g rec ok
ELE13-03211 Permanent Service11/19/201311/20/201311/20/2013 8:47:01 AMAPASS
BRENT Phone #: ###-#### p/s o/h rec ok