Inspections for the day of: Thursday, November 20, 2014.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03366 FIRE-Final Inspection11/17/201411/18/2014 P 
Elise// please call 45 min prior Phone #: ###-####
FIR14-00540 INSP-Sprinkler Rough-in11/19/201411/20/201411/20/2014 2:42:17 PMPPASS
Rough-in passed. Piping can not be covered until a tenting inspection has passed.
BLD14-03388 FIRE-Final Inspection11/19/201411/20/201411/20/2014 2:41:31 PMPFAIL
No access. I spoke to Linda and we are going to reschedule
FIR14-00661 INSP-Final Inspection11/19/201411/20/201411/20/2014 2:11:13 PMPCANC
To be canceled per Nathan Price and my discussion due to sync issues between the new and existing horns.
FIR14-00822 INSP-Sprinkler Rough-in11/19/201411/20/201411/20/2014 1:43:47 PMAPASS
Rough-in passed. Piping can be covered.
BLD14-03411 FIRE-Final Inspection11/19/201411/20/201411/20/2014 1:04:59 PMAPART
A temporary was given for life safety as per the scope of work. Bill claims Tim Woodard is ok with existing walls that are not shown on plans. I could not contact Tim. Bill shall provide verification to Building inspector of said conversation prior to a final sign off.
FIR14-00835 INSP-Sprinkler Rough-in11/19/201411/20/201411/20/2014 12:16:10 PMACANC
Cancel per Justin and mine discussion. Phone #: ###-####
FIR14-00735 INSP-Sprinkler Rough-in11/19/201411/20/201411/20/2014 12:15:36 PMAFAIL
This was for Bldg D dry system. Heads overspaced, additional fittings and heads blocked by obstructions. Plans need to be resubmitted that match the actual layout. No piping to be covered. Only inspected area at remote area. Did not look at hangers, bracing or restraints.
BLD14-02357 FIRE-Final Inspection11/19/201411/20/201411/20/2014 10:18:17 AMAPASS
life safety passed
FIR14-00679 INSP-Final Inspection11/19/201411/20/201411/20/2014 9:26:03 AMAFAIL
The new horns in the remodeled area do not sync with the existing horns in the other areas. Also there are exiting smoke detectors, which are over spaced, that are not shown on the city approved plans. A/v's tested ok with the activation of one of the existing smoke detectors. New NAC panel is supervised by the FACP.