FIR15-00601
| INSP-Sprinkler Rough-in/Hydro | 11/20/2015 | 11/20/2015 | 11/20/2015 2:54:27 PM | P | FAIL |
|
|
200 psi hydrostatic test performed on the underground supply, underground lost @16psi during the 2 hour hydrostatic test. Underground will have to retested.
|
FIR15-00601
| INSP-Sprinkler Rough-in/Hydro | 11/20/2015 | 11/20/2015 | 11/20/2015 2:51:42 PM | P | PASS |
|
|
200 psi hydrostatic test passed/complete for the 2 overhead wet systems.
|
BLD15-03348
| FIRE-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 1:07:51 PM | P | PASS |
|
|
No fire sprinklers for this project, no fire alarms for this project. Life fire safety passed/complete.
|
BLD15-02760
| FIRE-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 12:37:41 PM | A | PASS |
|
|
FIR permit inspection for fire sprinklers complete, FIR permit inspection for fire alarms complete. Life fire safety inspection passed/complete.
|
FIR15-00692
| INSP-Final Inspection | 11/20/2015 | 11/20/2015 | 11/20/2015 12:35:17 PM | P | PASS |
|
|
Devices associated with this permit completed under FIR15-00627, Webster Fire Protection. Devices for this tenant space tested on 20NOV2015, all devices passed inspection, inspection complete.
|
FIR15-00817
| INSP-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 11:31:15 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD15-01964
| FIRE-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 11:11:44 AM | A | PASS |
|
|
Fire sprinkler inspection for core/shell complete, fire alarm inspection for core/shell complete. Life fire safety inspection passed/complete.
|
FIR15-00627
| INSP-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 11:09:15 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR15-00702
| INSP-Final Inspection | 11/20/2015 | 11/20/2015 | 11/20/2015 11:08:15 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00610
| INSP-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 11:06:52 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00185
| INSP-Final Inspection | 11/19/2015 | 11/20/2015 | 11/20/2015 9:03:42 AM | A | PART |
|
|
Final inspection for 4th floor alarms passed/complete.
|
FIR15-00819
| INSP-Final Inspection | 11/19/2015 | 11/20/2015 | 11/19/2015 11:52:13 AM | A | CANC |
|
|
AES Fire Alarm Final Inspection Phone #: ###-#### >> Inspection requested via web by Jeremy Berg Inspection cancelled from web by: Jeremy Berg
|