BLD18-01746
| FIRE-Final Inspection | 11/20/2018 | 11/20/2018 | 11/20/2018 2:35:33 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection complete.
|
FIR17-00474
| INSP-Sprinkler Rough-in | 11/20/2018 | 11/20/2018 | 11/20/2018 2:31:55 PM | P | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink/pink highlighter areas approved for cover.
Contact is Mark Jensen Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR17-00753
| INSP-Final Inspection | 11/20/2018 | 11/20/2018 | 11/20/2018 2:30:11 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
ADAM Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR17-00753
| INSP-Sprinkler Rough-in | 11/20/2018 | 11/20/2018 | 11/20/2018 11:49:22 AM | P | PASS |
|
|
Notes for rough in and tenting were entered under the wrong permit, tenting notes were entered under FIR17-00427 on 13MAR2018
|
FIR18-00639
| INSP-Sprinkler Rough-in | 11/19/2018 | 11/20/2018 | 11/20/2018 11:44:57 AM | A | FAIL |
|
|
One head in main entry and one head in corridor between bedrooms are less than 4 inches off of wall, heads need to be relocated to be 4 inches or more from walls. Fire bell needs to be relocated to be seen from the address side of street. Need to perform hydrostatic test at city static pressure before final inspection can be completed.
John-overhead Phone #: ###-####
|
FIR18-00388
| INSP-Final Inspection | 11/20/2018 | 11/20/2018 | 11/20/2018 11:42:52 AM | A | PASS |
|
|
Final inspection for underground supply complete.
|
FIR18-00388
| INSP-Sprinkler Rough-in | 11/19/2018 | 11/20/2018 | 11/20/2018 11:42:23 AM | A | CANC |
|
|
John-underground Phone #: ###-####
|
FIR18-00388
| INSP-Supply line flush | 11/20/2018 | 11/20/2018 | 11/20/2018 11:41:43 AM | A | DONE |
|
|
Underground main line flush complete.
|
FIR18-00336
| INSP-Supply line flush | 11/20/2018 | 11/20/2018 | 11/20/2018 11:39:21 AM | P | DONE |
|
|
Supply line flush complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00583
| INSP-Sprinkler Rough-in | 11/19/2018 | 11/20/2018 | 11/20/2018 8:59:15 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in lobby and hardlid on level 2 complete, areas inspected approved for cover.
Tony Cetani is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00740
| INSP-Alarm Testing | 11/20/2018 | 11/20/2018 | 11/20/2018 8:56:05 AM | A | CANC |
|
|
Spoke with permit holding contractor, Micron needs more of a notice for fire alarm testing, alarm testing cannot be completed today based on conversation with Apex. This request is cancelled by request.
Call prior to going Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
|
FIR18-00769
| INSP-Sprinkler Rough-in | 11/19/2018 | 11/20/2018 | 11/20/2018 8:25:28 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, cover is approved.
Rick Phone #: ###-####
|
BLD18-01637
| FIRE-Final Inspection | 11/19/2018 | 11/20/2018 | 11/19/2018 1:59:53 PM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Rick Phone #: ###-####
|