ELE06-04040
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 4:19:44 PM | P | PASS |
|
|
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ok card signed
|
ELE06-04280
| Rough-In Permanent Service | 11/21/2006 | 11/21/2006 | 11/21/2006 3:35:59 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 9:39:08 AM. no p/s r/i for all walls and hard ceilings ok
|
ELE06-03025
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 3:35:14 PM | P | PASS |
|
|
mike ###-#### ok
|
ELE06-02088
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 2:57:07 PM | P | PASS |
|
|
mike ###-#### ok
|
ELE06-01390
| Electrical Rough-In | 11/17/2006 | 11/21/2006 | 11/21/2006 2:29:54 PM | P | FAIL |
|
|
mason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. met owner, 210.52(A) outlet spacing north wall, 300.14 6"free length, 110.26 subpanel shall be flush with finish for clearence, 314.43 no sscrews in plastic boxes, 210.70(A)(2)(b)light for exit door switch or automatic mean to turn off or on, 250.24(A)(5) isolate grds and neuts at subpanel, 250.148 grd metal boxes, 314.20 all boxes flush with wood finish, 314.27 needs listed fan boxes, 404.9 grd pigtail for all switches
|
ELE06-03823
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 12:59:23 PM | A | PASS |
|
|
dustin ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
ELE06-04335
| Conference | 11/20/2006 | 11/21/2006 | 11/21/2006 12:43:24 PM | A | DONE |
|
|
william -- ###-#### ok
|
ELE06-04320
| Rough-In Permanent Service | 11/21/2006 | 11/21/2006 | 11/21/2006 11:24:45 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS survey called 300.4 11/4" for SER, 334.23 protect cables attic accesses
|
ELE06-04218
| Permanent Service | 11/20/2006 | 11/21/2006 | 11/21/2006 11:01:09 AM | A | FAIL |
|
|
bill Note: please call for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr met contr. BCC & NEC mobile kitchen requires Idaho state tag yours only has Oregon, also no violations retained correct all wiring altered from manufactures wiring
|
ELE06-04040
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 10:52:42 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. called 110.3(B) use sq D breakers only, 406.4(D) outlets set back in steel plates, 408.4 needs panel directory noting location purpose and use
|
ELE06-02957
| Conference | 11/20/2006 | 11/21/2006 | 11/21/2006 9:49:39 AM | A | DONE |
|
|
don; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-04093
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 9:17:42 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/20/2006 at 1:00:59 PM. Contact: ###-####. ok pharmacy
|
ELE06-00711
| Electrical Rough-In | 11/21/2006 | 11/21/2006 | 11/21/2006 9:14:28 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 6:44:32 AM. Contact: ###-####. 3rd &4th floor walls anop
|
ELE06-04340
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 7:55:38 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|
ELE06-01438
| ELE-Aging Inspection | 11/21/2006 | 11/21/2006 | 11/21/2006 7:15:37 AM | | CANC |
|
|
wsuc
|
ELE05-03669
| ELE-Aging Inspection | 11/21/2006 | 11/21/2006 | 11/21/2006 7:14:52 AM | | PART |
|
|
wsuc
|
ELE04-01224
| ELE-Aging Inspection | 11/21/2006 | 11/21/2006 | 11/21/2006 7:14:28 AM | | CANC |
|
|
|
ELE04-01224
| DOC - Permit Expired | 11/21/2006 | 11/21/2006 | 11/21/2006 7:14:10 AM | A | PASS |
|
|
|
ELE06-04233
| Electrical Rough-In | 11/20/2006 | 11/21/2006 | 11/20/2006 1:16:39 PM | A | PASS |
|
|
timi; Phone #: ###-#### r/i ok owner will change out 14/3 on 20 amp circuit for 12/3, and install outside recept
|