Inspections for the day of: Tuesday, November 21, 2006.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04040 Final11/21/200611/21/200611/21/2006 4:19:44 PMPPASS
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ok card signed
ELE06-04280 Rough-In Permanent Service11/21/200611/21/200611/21/2006 3:35:59 PMPPART
Scheduled by a contractor via Hello! on 11/21/2006 at 9:39:08 AM. no p/s r/i for all walls and hard ceilings ok
ELE06-03025 Final11/21/200611/21/200611/21/2006 3:35:14 PMPPASS
mike ###-#### ok
ELE06-02088 Final11/21/200611/21/200611/21/2006 2:57:07 PMPPASS
mike ###-#### ok
ELE06-01390 Electrical Rough-In11/17/200611/21/200611/21/2006 2:29:54 PMPFAIL
mason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr. met owner, 210.52(A) outlet spacing north wall, 300.14 6"free length, 110.26 subpanel shall be flush with finish for clearence, 314.43 no sscrews in plastic boxes, 210.70(A)(2)(b)light for exit door switch or automatic mean to turn off or on, 250.24(A)(5) isolate grds and neuts at subpanel, 250.148 grd metal boxes, 314.20 all boxes flush with wood finish, 314.27 needs listed fan boxes, 404.9 grd pigtail for all switches
ELE06-03823 Final11/20/200611/21/200611/21/2006 12:59:23 PMAPASS
dustin ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE06-04335 Conference11/20/200611/21/200611/21/2006 12:43:24 PMADONE
william -- ###-#### ok
ELE06-04320 Rough-In Permanent Service11/21/200611/21/200611/21/2006 11:24:45 AMPPASS
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS survey called 300.4 11/4" for SER, 334.23 protect cables attic accesses
ELE06-04218 Permanent Service11/20/200611/21/200611/21/2006 11:01:09 AMAFAIL
bill Note: please call for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr met contr. BCC & NEC mobile kitchen requires Idaho state tag yours only has Oregon, also no violations retained correct all wiring altered from manufactures wiring
ELE06-04040 Final11/20/200611/21/200611/21/2006 10:52:42 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. called 110.3(B) use sq D breakers only, 406.4(D) outlets set back in steel plates, 408.4 needs panel directory noting location purpose and use
ELE06-02957 Conference11/20/200611/21/200611/21/2006 9:49:39 AMADONE
don; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-04093 Final11/20/200611/21/200611/21/2006 9:17:42 AMAPASS
Scheduled by a contractor via Hello! on 11/20/2006 at 1:00:59 PM. Contact: ###-####. ok pharmacy
ELE06-00711 Electrical Rough-In11/21/200611/21/200611/21/2006 9:14:28 AMAPART
Scheduled by a contractor via Hello! on 11/21/2006 at 6:44:32 AM. Contact: ###-####. 3rd &4th floor walls anop
ELE06-04340 Final11/21/200611/21/200611/21/2006 7:55:38 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE06-01438 ELE-Aging Inspection11/21/200611/21/200611/21/2006 7:15:37 AM CANC
wsuc
ELE05-03669 ELE-Aging Inspection11/21/200611/21/200611/21/2006 7:14:52 AM PART
wsuc
ELE04-01224 ELE-Aging Inspection11/21/200611/21/200611/21/2006 7:14:28 AM CANC
ELE04-01224 DOC - Permit Expired11/21/200611/21/200611/21/2006 7:14:10 AMAPASS
ELE06-04233 Electrical Rough-In11/20/200611/21/200611/20/2006 1:16:39 PMAPASS
timi; Phone #: ###-#### r/i ok owner will change out 14/3 on 20 amp circuit for 12/3, and install outside recept