ELE06-00921
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 4:14:55 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 8:30:47 AM. Contact: ###-####. called contr, about strapping rnc and gec into gen panel, survey, gen has been field evaluated, ok to final
|
ELE06-04355
| Electrical Rough-In | 11/21/2006 | 11/21/2006 | 11/21/2006 4:07:06 PM | P | PART |
|
|
Rough-in for restroom; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr about mc cable in valley of 2x6, issued as survey, walls only of bathrooms only ok to cover
|
ELE05-04191
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 4:05:09 PM | P | PASS |
|
|
Panel in large closet was looked at by 370, and per conversation with 324, determined that we will final the job due to ri confusion by owner and 370 regarding small room or dressing room or closet. There are no other outstanding issues, so ok to final.
|
ELE06-04345
| Electrical Rough-In | 11/20/2006 | 11/21/2006 | 11/21/2006 3:04:51 PM | P | CANC |
|
|
Work performed by Steve Johnson.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz talked to contr, said to cancel as the work was not done
|
ELE06-04099
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 2:25:44 PM | P | PASS |
|
|
BOB; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
ELE06-04324
| Temporary Service | 11/21/2006 | 11/21/2006 | 11/21/2006 1:46:09 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 8:22:37 AM. Contact: ###-####. called left corr notice nec 312.5 all conductors entering enclosure shall have abrasion protection, 590.6(B) 50A recpt shall be gfci protected
|
ELE06-04162
| Final | 11/21/2006 | 11/21/2006 | 11/21/2006 1:16:07 PM | P | PART |
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met elect, needs to finish panel schedule, tighten couple recpts, screw on faceplates, will call for final
|
ELE06-04047
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 12:33:25 PM | P | PASS |
|
|
trent; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left survey, nec 300.11(A) lv wiring shall not be supported by ceiling grid, ok to final, signed struct card
|
ELE06-04330
| Temporary Service | 11/20/2006 | 11/21/2006 | 11/21/2006 11:20:05 AM | A | PASS |
|
|
reinspect temporary power Internet Inspection Request from: Rowdy Monroe corr made, t/s u/g n ok
|
ELE06-04099
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 11:17:41 AM | A | FAIL |
|
|
dan ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called ,left corr notice, 404.9 shall provide faceplates for switch, 410.30.(C)(1) recpt shall be directly over fixture, 422.30 shall provide disc for water heater, 250.104 shall bond hot and cold water pipe, 110.3(B) gfci shall be installed per instruction
|
ELE06-04164
| Permanent Service | 11/20/2006 | 11/21/2006 | 11/21/2006 10:25:53 AM | A | PASS |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles checked for install after completed, ok, will do final on rest of house ltr
|
ELE06-03780
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 9:45:01 AM | A | FAIL |
|
|
jack ; Phone #: ###-#### Internet Inspection Request from: Patricia Smithcalled left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel, 680.26(B)(3) all metal fittings for pool cover shall be bonded, 680.22(A)(3) receptacle shall be between 10' and 20' of inside wall of pool
|
ELE06-04234
| Electrical Rough-In | 11/20/2006 | 11/21/2006 | 11/21/2006 9:10:17 AM | A | PASS |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok
|
ELE06-04126
| Electrical Rough-In | 11/20/2006 | 11/21/2006 | 11/21/2006 8:32:12 AM | A | PART |
|
|
this is for a ceiling inspection, any questions please call Jesse collingsworth; Phone #: ###-#### Internet Inspection Request from: Jeff Radford hard lids only ok to cover
|
ELE06-04110
| Electrical Rough-In | 11/20/2006 | 11/21/2006 | 11/21/2006 8:14:45 AM | A | FAIL |
|
|
Ceiling/restroom; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton called left message, left corr notice, nec 348.30 fmc shall be supported within 12" of termination, 300.11(A) raceways shall be supported securely, support wires tied top and bottom
|
ELE06-04069
| Final | 11/20/2006 | 11/21/2006 | 11/21/2006 8:02:19 AM | A | PASS |
|
|
shad ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final, signed card
|