Inspections for the day of: Tuesday, November 21, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00921 Final11/21/200611/21/200611/21/2006 4:14:55 PMPPASS
Scheduled by a contractor via Hello! on 11/21/2006 at 8:30:47 AM. Contact: ###-####. called contr, about strapping rnc and gec into gen panel, survey, gen has been field evaluated, ok to final
ELE06-04355 Electrical Rough-In11/21/200611/21/200611/21/2006 4:07:06 PMPPART
Rough-in for restroom; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr about mc cable in valley of 2x6, issued as survey, walls only of bathrooms only ok to cover
ELE05-04191 Final11/21/200611/21/200611/21/2006 4:05:09 PMPPASS
Panel in large closet was looked at by 370, and per conversation with 324, determined that we will final the job due to ri confusion by owner and 370 regarding small room or dressing room or closet. There are no other outstanding issues, so ok to final.
ELE06-04345 Electrical Rough-In11/20/200611/21/200611/21/2006 3:04:51 PMPCANC
Work performed by Steve Johnson.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz talked to contr, said to cancel as the work was not done
ELE06-04099 Final11/21/200611/21/200611/21/2006 2:25:44 PMPPASS
BOB; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
ELE06-04324 Temporary Service11/21/200611/21/200611/21/2006 1:46:09 PMPFAIL
Scheduled by a contractor via Hello! on 11/21/2006 at 8:22:37 AM. Contact: ###-####. called left corr notice nec 312.5 all conductors entering enclosure shall have abrasion protection, 590.6(B) 50A recpt shall be gfci protected
ELE06-04162 Final11/21/200611/21/200611/21/2006 1:16:07 PMPPART
Robert; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met elect, needs to finish panel schedule, tighten couple recpts, screw on faceplates, will call for final
ELE06-04047 Final11/20/200611/21/200611/21/2006 12:33:25 PMPPASS
trent; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left survey, nec 300.11(A) lv wiring shall not be supported by ceiling grid, ok to final, signed struct card
ELE06-04330 Temporary Service11/20/200611/21/200611/21/2006 11:20:05 AMAPASS
reinspect temporary power Internet Inspection Request from: Rowdy Monroe corr made, t/s u/g n ok
ELE06-04099 Final11/20/200611/21/200611/21/2006 11:17:41 AMAFAIL
dan ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called ,left corr notice, 404.9 shall provide faceplates for switch, 410.30.(C)(1) recpt shall be directly over fixture, 422.30 shall provide disc for water heater, 250.104 shall bond hot and cold water pipe, 110.3(B) gfci shall be installed per instruction
ELE06-04164 Permanent Service11/20/200611/21/200611/21/2006 10:25:53 AMAPASS
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles checked for install after completed, ok, will do final on rest of house ltr
ELE06-03780 Final11/20/200611/21/200611/21/2006 9:45:01 AMAFAIL
jack ; Phone #: ###-#### Internet Inspection Request from: Patricia Smithcalled left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel, 680.26(B)(3) all metal fittings for pool cover shall be bonded, 680.22(A)(3) receptacle shall be between 10' and 20' of inside wall of pool
ELE06-04234 Electrical Rough-In11/20/200611/21/200611/21/2006 9:10:17 AMAPASS
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok
ELE06-04126 Electrical Rough-In11/20/200611/21/200611/21/2006 8:32:12 AMAPART
this is for a ceiling inspection, any questions please call Jesse collingsworth; Phone #: ###-#### Internet Inspection Request from: Jeff Radford hard lids only ok to cover
ELE06-04110 Electrical Rough-In11/20/200611/21/200611/21/2006 8:14:45 AMAFAIL
Ceiling/restroom; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton called left message, left corr notice, nec 348.30 fmc shall be supported within 12" of termination, 300.11(A) raceways shall be supported securely, support wires tied top and bottom
ELE06-04069 Final11/20/200611/21/200611/21/2006 8:02:19 AMAPASS
shad ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final, signed card