Inspections for the day of: Friday, November 21, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-03093 Rough-In Permanent Service11/21/200811/21/200811/21/2008 4:00:07 PMPCANC
Late PM if possible Please
Thanks, Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl see added r/i , and p/s
ELE08-03093 Electrical Rough-In11/21/200811/21/200811/21/2008 3:59:44 PMPFAIL
Late PM if possible Please
Thanks, Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl called corr. 110.2, 110.3 (A&B) and BBC 4-05-33
shall provide 16" x 20" access as manufacture's instructions and j-tub shall be listed and so labeled
ELE08-03093 Permanent Service11/21/200811/21/200811/21/2008 3:57:07 PMPPASS
Late PM if possible Please
Thanks, Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl p/s u/g new ok
ELE08-01693 Final11/20/200811/21/200811/21/2008 3:55:56 PMPPASS
CONTACT: GREG PACK Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok no card
ELE08-00296 Final11/21/200811/21/200811/21/2008 2:37:19 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Karl Paige ok card signed
ELE08-02877 Electrical Rough-In11/21/200811/21/200811/21/2008 1:03:44 PMPPASS
tony Phone #: ###-#### ok
ELE08-02877 Rough-In Permanent Service11/21/200811/21/200811/21/2008 1:03:26 PMPPASS
tony Phone #: ###-#### r/i p/s u/g new ok
ELE07-03503 Final11/20/200811/21/200811/21/2008 11:23:09 AMAFAIL
dustin Phone #: ###-#### Note: please call 1/2 hr prior to inspection corr called 410.8 needs totally enclosed fixture MB closet, 410.4 needs shower trim, 406.3 and BCC needs gfci all replace recepts in kit. for countertops, 406. 4&5 recepts shall tight in boxes and flush with plates
ELE08-03083 Electrical Rough-In11/20/200811/21/200811/21/2008 11:19:11 AMAPART
inspect underground conduit to new shed & rough in of new shed. Any questions call George @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy okRose
ELE08-02348 Final11/20/200811/21/200811/21/2008 11:18:45 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok
ELE08-02866 Conference11/21/200811/21/200811/21/2008 9:13:53 AMADONE
Scheduled by a contractor via Hello! on 11/21/2008 at 12:59:12 AM. Contact: ###-####. ok note owner cut equip grd wires short
ELE08-02866 Electrical Rough-In11/21/200811/21/200811/21/2008 9:13:03 AMAPART
Scheduled by a contractor via Hello! on 11/21/2008 at 12:59:12 AM. Contact: ###-####. outside soffit lights ok
ELE08-02036 Permanent Service11/20/200811/21/200811/21/2008 8:34:24 AMAPASS
Inspection for Fire Pump Service. Job contact is Marc Benner. Phone #: ###-#### Internet Inspection Request from: Cyndi Dale Mickey check neutral bus at fire pump p/s p/s u/g new for fire pump service ok
ELE08-03079 Permanent Service11/20/200811/21/200811/20/2008 3:03:48 PMAPASS
permanent service and underground Phone #: ###-#### Internet Inspection Request from: Jenni Keller needs to address nipple between p/s and subpanel, also 4 wire , to range and drywe also 4wire pigtails and recepts for range and dryer p/s u/g rec. ok