FIR08-00574
| FIR-Aging Inspection | 11/21/2008 | 11/21/2008 | 11/24/2008 7:13:43 AM | | DEFR |
|
|
Work in progress
|
FIR07-01051
| INSP-Sprinkler Rough-in | 11/21/2008 | 11/21/2008 | 11/24/2008 7:11:39 AM | P | NH |
|
|
Rescheduled for 11/24 per discussion.
|
FIR08-00158
| INSP-Sprinkler Rough-in | 11/21/2008 | 11/21/2008 | 11/21/2008 5:01:34 PM | P | PART |
|
|
UG Cover okay per activity notes completed 6/27.
|
FIR08-00500
| INSP-Sprinkler Rough-in | 11/20/2008 | 11/21/2008 | 11/21/2008 4:58:25 PM | P | FAIL |
|
|
See red lines on plan set for areas in need of correction (2nd floor only inspected today) including an obstructed head at a janitors room, one missing arm-over hanger, heads overspaced at the restrooms, six overspaced heads at the southeast lounge room.
|
BLD08-01828
| FIRE-Final Inspection | 11/21/2008 | 11/21/2008 | 11/21/2008 4:50:34 PM | P | FAIL |
|
|
Missing building address numbers, hardware at the two exit doors is not approved, need to provide correct keys at the knox box.
|
BLD07-03049
| FIRE-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 3:05:56 PM | A | FAIL |
|
|
Missing one exit sign at the truckers lounge per red line annotation on approved building plan set, also missing the second fire hydrant as required per review note #3 and plan resubmittal sheet SD 1.0.
|
FIR08-00773
| INSP-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 3:03:15 PM | A | PASS |
|
|
Fire sprinkler work passed field inspection, permit finaled.
|
FIR07-00874
| INSP-Sprinkler Rough-in/Hydro | 11/20/2008 | 11/21/2008 | 11/21/2008 1:22:06 PM | A | FAIL |
|
|
Inspection for the aid station room only passed as initialed and red lined on plans, also noted one overspaced head and one obstructed head at the adjacent common corridor-see red line annotations.
|
BLD08-02270
| FIRE-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 1:19:17 PM | A | FAIL |
|
|
Provide approved door hardware at three exit doors on the first floor, repair one set of exit doors 1st floor south side, repair one non-funtional EM light at the main level west side, remove surface bolt at the basement level exit NE corner, provide a current annual inspection for the existing fire sprinkler and fire alarm systems, noted one SSU at a basement storage room to be relocated, noted missing drop ceiling tiles throughout the basement level-area separation is missing between upright and pendent sprinkler heads.
|
BLD08-02416
| FIRE-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 10:52:19 AM | A | PASS |
|
|
Life safety inspection completed satisfactory with the exception of the manul thumbturn at the back exit door to be removed or disabled prior to structural final inspeciton as agreed.
|
FIR08-00769
| INSP-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 10:48:53 AM | A | PASS |
|
|
Fire sprinkler work completed acceptable, permit finaled.
|
FIR08-00762
| INSP-Sprinkler Rough-in | 11/20/2008 | 11/21/2008 | 11/21/2008 10:47:18 AM | A | PART |
|
|
OH system modifications at the tenant remodel area are okay for cover except as red-lined on approved plans. Items include two overspaced arm-over hangers, one head at an office to be maintanted no more than 9' off an adjacent wall, noted two leaks to be repaired, one small room not yet completed.
|
BLD08-01133
| FIRE-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 12:00:00 AM | A | CANC |
|
|
JOE Phone #: ###-####
|