Inspections for the day of: Wednesday, November 21, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00757 FIR-Aging Inspection11/21/201211/21/201211/29/2012 9:40:05 AM NR
Contractor is out of business
FIR12-00385 FIR-Aging Inspection11/21/201211/21/201211/29/2012 9:17:09 AM NR
Mike is going to follow up on the project status and get back to me.
FIR12-00665 INSP-Sprinkler Rough-in11/21/201211/21/201211/21/2012 3:53:42 PMPPASS
See the city approved plans for piping that is ok to bury.
FIR12-00205 INSP-Sprinkler Rough-in11/21/201211/21/201211/21/2012 3:07:34 PMPPASS
See the city approved plans for the area in the existing building where the sprinkler piping is ok to cover.
BLD11-03016 FIRE-Final Inspection11/20/201211/21/201211/21/2012 2:30:15 PMAFAIL
All items except for the underground fuel tank sign off (by fire dept.) have been corrected.
FIR12-00423 INSP-Sprinkler Rough-in11/21/201211/21/201211/21/2012 1:57:35 PMPPASS
Tenting has been corrected and new plans have been approved. Piping can be covered except for the supply piping that crosses the breeze way at the first floor.
FIR12-00638 INSP-Sprinkler Rough-in/Hydro11/20/201211/21/201211/21/2012 1:17:49 PMPPART
The overhead hydro test failed due to a visable leak on the cpvc piping. The rough-in generaly passed except none of the tenting has been installed. Also the plans need to be resubmitted showing the 5 additional 90's between hydraulic node point 7 and 101. Also sprinkler coverage is required in the shower or a lintel of 8" as per our discussion. Piping can not be covered yet.
FIR12-00638 INSP-Sprinkler Rough-in/Hydro11/19/201211/21/201211/20/2012 2:51:35 PMACANC
This is an ug&oh hydro and rough to cover inspection. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR12-00638 INSP-Sprinkler Rough-in/Hydro11/19/201211/21/201211/19/2012 2:49:57 PMACANC
This is an ug hydro. Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus