Inspections for the day of: Friday, November 21, 2014.
Number of inspections: 7
Percentage of inspections complete: 86 %
Percentage of inspections not complete: 14 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00461 INSP-Sprinkler Rough-in/Hydro11/17/201411/18/2014 A 
Inspect fire sprinkler heat trace in basement. Call Jon Novak. Phone #: ###-#### >> Inspection requested via web by Tom Betty
FIR14-00500 INSP-Final Inspection11/20/201411/21/201411/21/2014 5:04:09 PMPPASS
Final walkthrough passed. Scope of fire sprinkler work completed. Permit finaled.
FIR14-00813 INSP-Final Inspection11/20/201411/21/201411/21/2014 5:03:11 PMPNR
Dave Phone #: ###-#### *Inspection request intended for a different project*
FIR14-00531 INSP-Sprinkler Rough-in11/20/201411/21/201411/21/2014 5:02:11 PMAPART
Rough-in inspection completed at "tower one" 5th floor room units 530,531,532,533,535,536, and 537, and common corridor including the elevator lobby. Noted items include; overspaced and obstructed head at unit 531 bedroom, relocate one sprinkler too close to a wall in unit 530, furnace rooms to be provided with intermediate temp heads, verify coverage at the elevator hoistway.
FIR14-00732 INSP-Sprinkler Rough-in11/20/201411/21/201411/21/2014 1:05:13 PMAPART
Overhead fire sprinkler modifications approved for cover at the tenant remodel area.
FIR14-00677 INSP-Sprinkler Rough-in11/20/201411/21/201411/21/2014 1:04:10 PMAPART
Noted items include; overspaced coverage at the SW conference room and the NE corridor. Need to adjust new pendent head at the breakroom drop ceiling. Refer to stamped plans for dated annotations. Remainder of work okay for cover.
FIR14-00835 INSP-Sprinkler Rough-in11/20/201411/21/201411/21/2014 12:59:58 PMAPART
Overhead work approved for cover at the sheetrock lid ceilings as marked and dated on stamped plans. Need plan modification for deleted heads prior to permit final as discussed.