Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF16-00032 INSP-Final11/21/201611/21/201611/21/2016 4:41:19 PMPFAIL
Verified all devices. Xray room missing a device, device on balcony was not functioning, and pressure switch on dry system not connected to bell. Smokes at main panel and riser room to be tested as well.

-RTU detectors were tested, OK
-Elevator recall tested, OK
-All Tampers, Flows tested
NAF16-00023 INSP-Final11/18/201611/21/201611/21/2016 4:38:16 PMPPASS
Previous correction items completed. Air Test was completed on 9/20/16. System test completed satisfactory. Scope of work complete. Permit Finaled.
NAF16-00032 INSP-Final11/16/201611/21/201611/21/2016 4:36:51 PMAPASS
All previous correction items were completed. Air Test had been completed previously on 9/20/16. System test completed satisfactory. Scope of work complete. Permit Finaled.
NAF16-00057 INSP-Sprinkler Rough-in11/17/201611/21/201611/21/2016 10:07:20 AMAPART
24 air test began at 9:40 am on 11/21/16. Pressure was 42psi