NAF16-00032
| INSP-Final | 11/21/2016 | 11/21/2016 | 11/21/2016 4:41:19 PM | P | FAIL |
|
|
Verified all devices. Xray room missing a device, device on balcony was not functioning, and pressure switch on dry system not connected to bell. Smokes at main panel and riser room to be tested as well.
-RTU detectors were tested, OK -Elevator recall tested, OK -All Tampers, Flows tested
|
NAF16-00023
| INSP-Final | 11/18/2016 | 11/21/2016 | 11/21/2016 4:38:16 PM | P | PASS |
|
|
Previous correction items completed. Air Test was completed on 9/20/16. System test completed satisfactory. Scope of work complete. Permit Finaled.
|
NAF16-00032
| INSP-Final | 11/16/2016 | 11/21/2016 | 11/21/2016 4:36:51 PM | A | PASS |
|
|
All previous correction items were completed. Air Test had been completed previously on 9/20/16. System test completed satisfactory. Scope of work complete. Permit Finaled.
|
NAF16-00057
| INSP-Sprinkler Rough-in | 11/17/2016 | 11/21/2016 | 11/21/2016 10:07:20 AM | A | PART |
|
|
24 air test began at 9:40 am on 11/21/16. Pressure was 42psi
|