Inspections for the day of: Tuesday, November 21, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03026 Electrical Rough-In11/21/201711/21/201711/21/2017 3:14:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
2nd warning for cover prior to inspection. Contractor supplied ladder. Final warning. Grid rough in ok cover
ELE17-01949 Final11/21/201711/21/201711/21/2017 3:13:03 PMPFAIL
Contact Jose Phone #: ###-#### Inspection requested via web by Kevin Perez
300.4(E)- EMT raceways shall not be installed with in 1 1/2" of roof deck. If new or reused raceways they shall comply with current code cycle.
358.30- EMT shall be secured with in 3' of a box or conduit body.
ELE16-03350 Final11/16/201711/21/201711/21/2017 1:03:21 PMPPASS
aging Phone #: ###-#### Inspection requested via web by Steve VanWinkle
Final ok
ELE16-03350 Electrical Rough-In11/21/201711/21/201711/21/2017 1:03:15 PMPPASS
aging Phone #: ###-#### Inspection requested via web by Steve VanWinkle
Listing confirmed rough in ok
ELE17-03066 Final11/20/201711/21/201711/21/2017 11:06:11 AMAFAIL
We are requesting a final inspection for tomorrow morning. Our contact is Bryant at ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
210.8(B)- All receptacle outlets located in kitchens shall have GFCI protection. Panini press 20 amp 208 volt receptacle.
314.25- All boxes shall have covers. Bath vanities, south room,
ELE17-03667 Final11/20/201711/21/201711/21/2017 10:43:06 AMAPASS
We can get in there between 9:45 am and 1:40 pm. Corrections made. Please call so I can meet ya! Thanks, Rex. Phone #: ###-#### Inspection requested via web by Rex Boyles Final ok
ELE17-03943 Electrical Rough-In11/20/201711/21/201711/21/2017 10:13:02 AMAPASS
please inspect under ground conduit for phone and cable for cover. Thanks! Phone #: ###-#### Inspection requested via web by Robert Schroder
2" and 3/4" going in on this unit as well as one to west 36" deep underground rough in ok cover
ELE17-01755 Final11/20/201711/21/201711/21/2017 9:49:09 AMAPASS
Please call 30 min prior to have someone meet you there. Thank yoh Phone #: ###-#### Inspection requested via web by Tom Jenkins
No card posted. Final ok
ELE17-03579 Final11/20/201711/21/201711/21/2017 9:33:59 AMAFAIL
Jason is the contact his cell no is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates
314.25- All boxes shall have covers. box located on patio open.
406.4(D)- Still have grounding type receptacle outlets on ungrounded circuits with out GFCI protection.
406.4(D)- All grounding type receptacles on ungrounded circuits shall be labeled " no equipment ground and GFCI protected".
ELE17-03066 Final11/20/201711/21/201711/20/2017 3:47:43 PMPCANC
We are requesting a final inspection. Bryant is our contact ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate