ELE17-03026
| Electrical Rough-In | 11/21/2017 | 11/21/2017 | 11/21/2017 3:14:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 2nd warning for cover prior to inspection. Contractor supplied ladder. Final warning. Grid rough in ok cover
|
ELE17-01949
| Final | 11/21/2017 | 11/21/2017 | 11/21/2017 3:13:03 PM | P | FAIL |
|
|
Contact Jose Phone #: ###-#### Inspection requested via web by Kevin Perez 300.4(E)- EMT raceways shall not be installed with in 1 1/2" of roof deck. If new or reused raceways they shall comply with current code cycle. 358.30- EMT shall be secured with in 3' of a box or conduit body.
|
ELE16-03350
| Final | 11/16/2017 | 11/21/2017 | 11/21/2017 1:03:21 PM | P | PASS |
|
|
aging Phone #: ###-#### Inspection requested via web by Steve VanWinkle Final ok
|
ELE16-03350
| Electrical Rough-In | 11/21/2017 | 11/21/2017 | 11/21/2017 1:03:15 PM | P | PASS |
|
|
aging Phone #: ###-#### Inspection requested via web by Steve VanWinkle Listing confirmed rough in ok
|
ELE17-03066
| Final | 11/20/2017 | 11/21/2017 | 11/21/2017 11:06:11 AM | A | FAIL |
|
|
We are requesting a final inspection for tomorrow morning. Our contact is Bryant at ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate 210.8(B)- All receptacle outlets located in kitchens shall have GFCI protection. Panini press 20 amp 208 volt receptacle. 314.25- All boxes shall have covers. Bath vanities, south room,
|
ELE17-03667
| Final | 11/20/2017 | 11/21/2017 | 11/21/2017 10:43:06 AM | A | PASS |
|
|
We can get in there between 9:45 am and 1:40 pm. Corrections made. Please call so I can meet ya! Thanks, Rex. Phone #: ###-#### Inspection requested via web by Rex Boyles Final ok
|
ELE17-03943
| Electrical Rough-In | 11/20/2017 | 11/21/2017 | 11/21/2017 10:13:02 AM | A | PASS |
|
|
please inspect under ground conduit for phone and cable for cover. Thanks! Phone #: ###-#### Inspection requested via web by Robert Schroder 2" and 3/4" going in on this unit as well as one to west 36" deep underground rough in ok cover
|
ELE17-01755
| Final | 11/20/2017 | 11/21/2017 | 11/21/2017 9:49:09 AM | A | PASS |
|
|
Please call 30 min prior to have someone meet you there. Thank yoh Phone #: ###-#### Inspection requested via web by Tom Jenkins No card posted. Final ok
|
ELE17-03579
| Final | 11/20/2017 | 11/21/2017 | 11/21/2017 9:33:59 AM | A | FAIL |
|
|
Jason is the contact his cell no is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates 314.25- All boxes shall have covers. box located on patio open. 406.4(D)- Still have grounding type receptacle outlets on ungrounded circuits with out GFCI protection. 406.4(D)- All grounding type receptacles on ungrounded circuits shall be labeled " no equipment ground and GFCI protected".
|
ELE17-03066
| Final | 11/20/2017 | 11/21/2017 | 11/20/2017 3:47:43 PM | P | CANC |
|
|
We are requesting a final inspection. Bryant is our contact ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|