Inspections for the day of: Tuesday, November 21, 2017.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-05224 Final11/20/201711/21/201711/21/2017 4:12:37 PMPNH
replace furnace Phone #: ###-#### Inspection requested via web by Aaron Alandt- no access- no one home
MEC17-05234 Final11/20/201711/21/201711/21/2017 3:36:41 PMPCANC
CALL INSTALLER, DWIGHT, TO ENSURE INSTALL IS COMPLETED BEFORE GOING - ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- scheduled for wrong day- will reschedule
MEC17-05192 Final11/21/201711/21/201711/21/2017 3:18:53 PMPNH
please call when you are on the way Phone #: ###-#### Inspection requested via web by Marisa Hone- called # listed no answer- went by no one home
MEC17-04122 Final11/21/201711/21/201711/21/2017 2:36:50 PMPPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- final ok- will final out after other mech permit has been inspected for TVR
MEC17-05055 Final11/17/201711/21/201711/21/2017 2:00:10 PMPPASS
She would like early afternoon if at all possible. Phone #: ###-#### Inspection requested via web by Stephanie Phillippi
MEC17-04321 Final11/21/201711/21/201711/21/2017 1:41:56 PMAPASS
MEC17-04321 Final11/21/201711/21/201711/21/2017 1:39:17 PMPPASS
MEC17-04321 Rough-in11/20/201711/21/201711/21/2017 1:35:44 PMPPASS
The later the better. Thank you. Phone #: ###-#### Inspection requested via web by Troy Nichols- fireplace and fluing ok
MEC17-05215 Pressure Test11/20/201711/21/201711/21/2017 11:42:11 AMAFAIL
Contact: Aaron (QHC) @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley- not holding pressure- dante valve no good will replace and call back in for inspection
MEC17-05118 Rough-in11/20/201711/21/201711/21/2017 10:29:49 AMAFAIL
Inspection requested via web by Konrad Swartz- need approved manual J onsite for inspection- all bare copper on line set needs rips and tears fixed on lineset from furnace to outside- flexible duct needs to be installed per manufacture installation manul missing mechanical fasteners on ALL flex connections
MEC17-05118 Pressure Test11/20/201711/21/201711/21/2017 10:25:47 AMAPASS
Inspection requested via web by Konrad Swartz- 20lb gas pass
MEC17-03733 Final11/21/201711/21/201711/21/2017 10:06:01 AMAFAIL
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need duct blast completed and signed off to final out
MEC16-04655 Mec-Aging Inspection11/21/201711/21/201711/21/2017 9:10:35 AM FAIL
no calls- no one home- no access- left notice front door
MEC16-03297 Mec-Aging Inspection11/21/201711/21/201711/21/2017 8:52:50 AM DONE
MEC16-03297 Final11/21/201711/21/201711/21/2017 8:52:37 AMAPASS
MEC17-04321 Rough-in11/19/201711/21/201711/20/2017 6:17:29 PMACANC
Phone #: ###-#### >> Inspection requested via web by Troy Nichols Inspection cancelled from web by: Troy Nichols
MEC17-05181 Rough-in11/16/201711/21/201711/17/2017 6:25:08 PMACANC
BRAXTON ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Robinson Inspection cancelled from web by: Jason Robinson