Inspections for the day of: Tuesday, November 21, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-02147 FIRE-Final Inspection11/21/201711/21/201711/24/2017 10:23:56 AMPFAIL
Still waiting for Opticon erification for the gates

Phone #: ###-#### Inspection requested via web by Jeff Hannes
NAF17-00072 INSP-Final11/20/201711/21/201711/21/2017 2:34:29 PMPDONE
Permit finaled. Suppression system functioned correctly
BLD17-01593 FIRE-Final Inspection11/20/201711/21/201711/21/2017 9:45:22 AMAPASS
Life safety passed

Mandee Phone #: ###-####
BLD17-04209 FIRE-Final Inspection11/20/201711/21/201711/21/2017 9:24:58 AMAFAIL
LIfe safety will be ok to final when a separate fire alarm permit is finaled for the overspaced ceiling mounted strobe in the Office/BreakRoom.

Marva Phone #: ###-####
FIR17-00432 INSP-Sprinkler Rough-in11/20/201711/21/201711/21/2017 8:29:39 AMAPASS
The exterior canopies have been fire blocked to less than 160 cubic feet. They are ok for cover.
FIR17-00656 INSP-Final Inspection11/20/201711/21/201711/21/2017 8:03:45 AMAFAIL
Project is not ready for a final. Todays inspection was just for a rough-in. Hard lids are ok to cover. The remaining piping is not ok for cover. I noted three overspaced pendant heads in the large open area.