Inspections for the day of: Wednesday, November 21, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04463 Final11/21/201811/21/201811/21/2018 1:17:50 PMPPASS
Afternoon inspection, please; so I have time to get underground in place. Phone #: ###-#### Inspection requested via web by shane miller...
service outlet..ok
panel labelled...ok
ok to final
ELE18-04463 Electrical Rough-In11/19/201811/21/201811/21/2018 1:14:35 PMPPASS
Afternoon inspection, please; so I have time to get underground in place. Phone #: ###-#### Inspection requested via web by shane miller...
circuit wired from back panel, PVC underground, 25A circuit to discount...ok
ELE18-03368 Final11/20/201811/21/201811/21/2018 10:35:13 AMAPASS
Garage code 7373 Phone #: ###-#### Inspection requested via web by Heath Thomas...
ok to final
ELE18-03452 Final11/20/201811/21/201811/21/2018 10:34:42 AMAPASS
Garage code 7373 Phone #: ###-#### Inspection requested via web by Heath Thomas...
ok to final
ELE18-04485 Rough-In Permanent Service11/20/201811/21/201811/21/2018 10:03:20 AMPPASS
Please call when done so I can fill in the trench 208 860 9185 Phone #: ###-#### Inspection requested via web by Thomas wilson
p/s u/g new ok
ELE18-04403 Electrical Rough-In11/21/201811/21/201811/21/2018 9:52:38 AMAPASS
We have rough in electrical ready for warehouse wall and bathroom wall. please call me 30 minutes in advance to ensure I can meet you on site. Phone #: ###-#### Inspection requested via web by Casey Fouts...
ok to cover
existing wall with new circuits
added outlets and changed out outlets for GFI protection are good
floor outlets check at final
ELE18-04319 Final11/20/201811/21/201811/21/2018 9:08:33 AMAPASS
final for new parking lot lights...6 new heads...complete...ok to final
ELE18-04431 Permanent Service11/21/201811/21/201811/21/2018 8:34:48 AMPCANC
Service Upgrade inspection Any questions please call Jordan at ###-#### Phone #: ###-#### >> Inspection requested via web by Louis Keller Inspection cancelled from web by: Louis Keller
ELE18-03449 Final11/20/201811/21/201811/21/2018 8:16:50 AMAPASS
Phone #: ###-#### Inspection requested via web by John VanZandt...corrections made...ok to final
ELE18-04375 Conference11/20/201811/21/201811/20/2018 1:07:41 PMAPASS
Shoot, I just missed the 11:30 deadline. Is there any way an inspector could come today? Inspection requested via web by Stephen Morley...
discussed requirements for new meter base
grounding needs updated 2 ground rods 6ft apart with #6 wire , expansion joint, intersystem bond bridge, and strapping
pamphlet given...homeowner knowledgeable