Inspections for the day of: Friday, November 22, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02262 FIRE-Final Inspection11/21/200211/22/200211/22/2002 12:00:00 AMAPASS
###-#### doug
MIS02-00304 FIR-Final11/21/200211/22/200211/22/2002 12:00:00 AMAPASS
RHONDA ###-####
BLD02-02395 FIRE-Final Inspection11/21/200211/22/200211/22/2002 12:00:00 AMAPASS
FIR02-00300 INSP-Final Inspection11/21/200211/22/200211/22/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 11/21/2002 at 08:38:37. Contact: ###-####. relocate AV to within 15 ft of corridor; recalc NAC's; gym overspaced for strobe placement; need knox box and map at panel; NAC's not temporal; need to test inittiating and av equipment in out buildings 11/22/2002 5:18:43 PM