Inspections for the day of: Tuesday, November 22, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02068 Final11/22/200511/22/200511/22/2005 6:42:25 PMPPASS
after 3 please///ron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
ELE05-03742 Final11/22/200511/22/200511/22/2005 4:08:01 PMPPASS
After 3:PM please Or call prior dispatch; Phone #: ###-#### Internet Inspection Request from: Jim Woodhead ok to final
ELE05-03534 Electrical Rough-In11/22/200511/22/200511/22/2005 3:58:15 PMPFAIL
Ceiling inspection Pink Salon 6914 W. State; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, left corr notice, told ok to cover part of clg since he would call for am inspection, 330.30(B) mc cable shall be secured within 12" of box, 358.30(A) emt shall be secured within 3' of box, 210.62 show window recpt shall be added to east of door,725.3(B) abandoned lv cable shall be removed
ELE05-03661 Final11/22/200511/22/200511/22/2005 2:47:35 PMPNR
Scheduled by a contractor via Hello! on 11/22/2005 at 9:47:54 AM. Contact: ###-####. will recall
ELE05-03780 Final11/22/200511/22/200511/22/2005 1:39:44 PMPPASS
Scheduled by a contractor via Hello! on 11/22/2005 at 9:49:05 AM. Contact: ###-####. signed occ card, ok to final
ELE05-03591 Final11/22/200511/22/200511/22/2005 1:39:05 PMPPART
Scheduled by a contractor via Hello! on 11/22/2005 at 11:00:43 AM. Contact: ###-####. signed temp occ card, outstanding corr notice.
ELE05-04227 Temporary Service11/21/200511/22/200511/22/2005 9:54:05 AMAPASS
Contact: Eric Cobiskey; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called contr about gnd rod diameter, t/s o/h n ok
ELE05-03384 Rough-In Permanent Service11/22/200511/22/200511/22/2005 9:51:25 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ric ok, corrections made, p/s u/g n ok
ELE05-03357 Final11/21/200511/22/200511/22/2005 9:16:17 AMAPASS
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ok to final
ELE05-03780 Final11/21/200511/22/200511/22/2005 8:30:44 AMAPART
Scheduled by a contractor via Hello! on 11/21/2005 at 4:50:25 PM. Contact: ###-####. ok to cover rear ceiling, need to check front to final, need to check j-box repair, firm mount j-box under counter